MPC Open XP specifications

Driver
Maximum number of control
programs*
Maximum number of
BACnet objects*
Maximum number of third-
party integration points
using Snap*†
* Depends on available memory
† BACnet third-party integration points are not counted.
* Depends on available
memory
†BACnet third-party
integration points are
unlimited
Power
BACnet port
Rnet port
Local Access port
Xnet Remote Expansion port For communication with expanders MPC Open XPIO48 and/or MPC Open
Inputs
Input resolution
Input pulse frequency
Outputs
Output resolution
MPC Open XP
MPC Open XP IO48/816
Installation and Start-up Guide
drv_mpcxpopen_vanilla_x-xxx-xxx
999
12000
200
24 Vac ±10%, 50–60 Hz
50 VA power consumption
26 Vdc (25 V min, 30 V max), 23 W
Single Class 2 source only, 100 VA or less
For communication with the controller network using BACnet ARC156 (156
kbps) or BACnet MS/TP (9600 bps – 76.8 kbps)
Supports:
Up to 15 ZS sensors (5 per control program)
One Wireless Adapter that communicates with up to 15 Wireless sensors
One Equipment Touch
Up to 4 SPT Standard sensors and one SPT Plus, SPT Pro, or SPT Pro-F
sensor
NOTE ZS sensors, a Wireless Adapter, and an Equipment Touch can share the
Rnet, but not SPT sensors.
For system start-up and troubleshooting using Field Assistant or an Equipment
Touch device
XPIO816. Up to 3 expanders with a maximum of 92 points between the MPC
Open XP and the expanders.
12 inputs, configurable for 0–5 Vdc, 0–10 Vdc, 0–20 mA, RTD, thermistor, or dry
contact
14 bit A/D
40 pulses per second. Minimum pulse width (on or off time) required for each
pulse is 12.5 msec.
8 outputs for 24 Vdc relay driver, 0–10 Vdc, or 0-20 mA. Does not support dry
contact output channels.
12 bit D/A
Carrier Proprietary and Confidential
3
Introduction
CARRIER CORPORATION ©2017