Specifications

Driver
Maximum number of control programs*
Maximum number of BACnet objects*
Third-party BACnet integration points
Third-party Modbus integration points
* Depends on available memory.
Power
I/O expanders
Gig-E port
Port S1
Port S2
Rnet port
I/O Bus port
I/O bus edge connector
Xnet port
TruVu™ ChillerVu™ Plant Controller
Installation and Start-up Guide
drv_fwex_< version >.driverx
999
12000
1500
1000
24 Vac ±10%, 50–60 Hz, 50 VA
26 Vdc ±10%, 15 W
Supports up to 9 TruVu
TM
MPC I/O expanders and/or 6 MPC Open XPIO expanders,
but no more than 9 expanders total.
10/100/1000 BaseT, full duplex, Ethernet port for BACnet/IP and/or
BACnet/Ethernet, or Modbus TCP/IP communication.
For communication with either of the following:
A BACnet ARCNET network at 156 kbps
A BACnet MS/TP network at 9600 to 115200 bps
A Modbus serial network at 9600 to 115200 bps
This port's End of Net? switch can be set to Yes to terminate the network segment.
For communication with either of the following:
A BACnet MS/TP network at 9600 to 115200 bps
A Modbus serial network at 9600 to 115200 bps
This port's End of Net? switch can be set to Yes to terminate the network segment.
Supports Up to 15 ZS wireless and/or ZS sensors, and one Equipment Touch
or TruVu™ ET Display
Supports local connection for a laptop running the i-Vu® application
Supplies 12 Vdc/62.5 mA power across its rated temperature range.
NOTE Ambient temperature and power source fluctuations may reduce the
power supplied by the Rnet port.
NOTE If the total power required by the sensors on the Rnet exceeds the power
supplied by the Rnet port, use an external power source. The Wireless Adapter,
Equipment Touch, or TruVu™ ET Display must be powered by an external power
source. See the specifications in each device's Installation and Start-up Guide to
determine the power required.
Provides communication for a wired TruVu
an external power supply. See TruVu
to determine how many TruVu
6-pin connector that provides communication and power to a directly-connected
TM
TruVu
MPC I/O expander. See TruVu
9) to determine how many TruVu
connector.
For communication with up to 6 MPC Open XPIO expanders powered by an external
power supply.
3
What is the TruVu™ ChillerVu™ Plant Controller?
TM
MPC I/O expander that is powered by
TM
MPC I/O expander configurations (page 9)
TM
MPC I/O expanders you can connect to this port.
TM
MPC I/O expander configurations (page
TM
MPC I/O expanders you can use with the edge
©2022 Carrier.
All rights reserved.