8.16 External Auxiliary Settings (Bild 04.00)

The ozone system offers the possibility to connect an external device which is operated with
the ozone system. The external device starts and stops automatically depending on the
system sequence of the ozone system.
The start signal is given with the sequence step: Start gas flow.
The stop signal is given with the sequence step Stop gas flow.
The basic settings of the external auxiliary can be changed in this menu level. Basic settings
are Operating Mode, Status and Turn off Delay after stopping the ozone production.
Operating Mode
Automatic
Manual
The ozone system cannot be operated if at least one external auxiliary is in
Manual Mode. This state is indicated by the operating message:
"System not ready for operation. At least one device not in Automatic Mode"
Manual_SMOevoPLUS_eng_01.2019.doc
The external auxiliary may always be operated in Automatic Mode,
i.e. start and shutdown is carried out automatically via the start and
stop sequence.
If the external auxiliary is stopped in Automatic Mode, it turns off not
before the preset delay time has elapsed.
The Manual Mode is a kind of maintenance function. In Manual
Mode, an On/Off switch appears allowing to start or shut down the
external auxiliary manually.
Starting and stopping is immediate and without a delay time .
Manual Ozone Generating System SMOevo
PLUS
Operation