Production Settings (Screen 03.00.03) Required Ozone Mass - Xylem WEDECO SMOevo PLUS Series Original Manual

Ozone generating system
Table of Contents

Advertisement

8.13 Production Settings (Screen 03.00.03) Required Ozone
Mass
Production Settings screen with control mode Required Ozone Mass
With this control mode, in addition to the main setpoint Required Ozone mass, a further constant
setpoint must be specified: the Ozone Concentration or the Gas Flow Generator. Depending on
the ozone requirement, the non-constant setpoint is changed variably in order to produce the
Required Ozone Mass.
Signals
(Setpoint)*
Gas Flow
Ozone
Conzentration
Required
Ozone Mass
*the main setpoint is the Required Ozone Mass. The constant setpoint must be set
accordingly depending on the production mode. In the Remote mode (Hardwired), only the
main setpoint is set via a 4...20 mA signal. The constant setpoint must be entered locally on
the touch panel. In the Remote mode (Network), the main setpoint and the constant setpoint
must be specified via the network signal depending on the production mode. The variable
parameter is automatically calculated by the ozone system.
Manual_SMOevoPLUS_eng_01.2019.doc
Remote
Local
(Hardwired)
x
X
X
4W20 mA = 0WX g/h
Ozone production
Manual Ozone Generating System SMOevo
Remote
(Network)
-
x
-
X
X
X
PLUS
Operation
Remote
(Wedecontrol
)
x
X
X
page 102 of 179