Production Mode
Dose Control
With this control mode, in addition to the main setpoint Ozone Dose, another constant setpoint
must be specified: Ozone Concentration or Gas Flow Generator.
Depending on the Required Ozone Mass, the non-constant setpoint is changed variably in order
to produce the Required Ozone Mass. The Process Water Flow is the reference variable for
determining the required mass.
Signal
(Setpoint)
Gas Flow
Generator
Ozone
Concentration
Ozone Dose
Process Water
Flow
Manual_SMOevoPLUS_eng_01.2019.doc
With the Dose Control, an Ozone Dose per m³/h process water
flow is specified as the main setpoint.
By multiplying the Ozone Dose by the process water flow, the
Required Ozone Mass is obtained.
Remote
Local
(Hardwired)
X
-
X
-
X
-
X
X
4W20 mA = 0WX
m³/h Process Water
Flow
Manual Ozone Generating System SMOevo
Remote
(Network)
X
X
X
X
PLUS
Operation
Remote
(Wedecontrol)
X
X
X
X