Fujitsu PRIMERGY TX1330 M4 Upgrade And Maintenance Manual page 153

Hide thumbs Also See for PRIMERGY TX1330 M4:
Table of Contents

Advertisement

Tools:
tool-less
CAUTION
When replacing a PSU in a non-redundant PSU configuration, the
server must be switched off first.
Replace the PSU after specifying the one that breaks down at work
by revitalization.
Note for servers using CMA (Cable Management Arm)
Regarding of removing PSUs, additional tasks are needed, due to an
interference between CMA and the PSUs.
▶ If applicable, open the CMA of the server below to get enough space at the
under side of your server.
▶ Unlock the CMA stopper of the server below.
▶ Pull out the CMA of the server below to the rear side.
▶ Push the lock spring inward to unlock the CMA bracket, see
▶ Remove the CMA.
▶ Hold the CMA including cables in the one hand.
▶ Remove the PSU (see
▶ Mount the complete assembly (CMA bracket and the CMA) again into the
rail.
▶ If applicable, close the CMA of the server below.
Preliminary steps
"Locating the defective server" on page
▶ Check which PSU is defective.
PSU is defective when the PSU status indicator lights orange. For more
information, see
▶ Only when replacing a PSU in a non-redundant configuration:
down the server" on page
TX1330 M4
Figure
72) and install the new PSU carefully.
"Indicator on hot-plug PSU" on page
47.
Upgrade and Maintenance Manual
Power supply unit (PSU)
45.
511.
Figure
70.
"Shutting
153