Remote Control for Owner's Please read this manual BEFORE Manual Evolution Series operating. Inverter/ Charger Model: EVO-RC-PLUS Firmware Version: 0.33 NOTE: REMOTE CONTROL MODEL NO. EVO-RC-PLUS IS OPTIONAL AND IS REQUIRED TO BE ORDERED SEPARATELY.
Introduction and Layout 1.0 INTRODUCTION EVO-RC-PLUS Remote Control is used to monitor and customize the operating parameters of Samlex EVO™ Inverter/ Chargers Model (i) EVO-1212F / 1212F-HW / 1224F / 1224F-HW, (ii) EVO-2212 / 3012 / 2224 / 4024 (iii) EVO-2212E / 3012E / 2224E / 4024E and (iv) EVO-4248SP.
Page 4
1 2 3 4 5 6 7 8 123456 1 2 3 4 5 6 7 8 RJ-12 (6P6C) Jack RJ-45 (8P8C) Jack Fig 1.3 Pinout and internal interconnections of RJ-45 (8P8C) and RJ-12 (6P6C) Jacks on EVO-RC-PLUS 4 | SAMLEX AMERICA INC.
Page 5
[Fig 1.4] and rewired as shown Connect to “A-6P4C” Connect to RJ-45 Jack 6P6C Jack on marked “Remote Control” EVO-RC-PLUS 1 2 3 4 5 6 1 2 3 4 5 6 7 8 on (i)EVO-2212/3012/2224/4024 Black Black or, (ii)EVO-2212E/3012E/2224E/4024E...
SECTION 2 | Installation 2.0 INSTALLATION GUIDELINES EVO-RC-PLUS is provided with 10M/33ft, RJ-45 data cable (straight wired). Check the proposed routing distance of the wire and use longer wire, if necessary. • Flush mounting of the Remote requires appropriate cut-out in the wall/panel - See Fig 2.1.
Page 7
3. Route one end of the cable through wall opening to the EVO™ Inverter/Charger, and then plug it into the RJ-45 Remote Control Jack port on the EVO™ Inverter/Charger 4. Take the other end of the remote cable and plug it into the RJ-45 / RJ-12 Jack at the back of the EVO-RC-PLUS (Fig. 2.3).
Operation 3.0 GENERAL INFORMATION EVO-RC-PLUS Remote Control provides the user with the ability to monitor the operation and also to modify EVO™ Inverter/Charger’s operating parameters. The default settings in EVO™ Inverter/Charger are adequate for some installations but may have to be modified for others. This Section provides details on the remote functions, status and menu maps and displays, fault messages and parameter settings.
Page 9
To power OFF the EVO™ Inverter/Chargers manually using the ON/OFF Button on the front panel of the unit or the ON/OFF Key on the Remote-Control EVO-RC-PLUS, there should be no AC input voltage or, has to be less than the limits shown in the Table below.
Page 10
"Standby Mode" Screens show in Figs 3.1(a) / 3.1(b). e) Press the On/Off Push Button (2, Fig 1.1) on the EVO-RC-PLUS to exit the "Standby Mode" to the current operating mode. Refer to Section 3.4 for more details on "Standby Mode".
Page 11
Inverter/Charger Unit to enter Standby Mode as explained at Section 3.4.1.1 below. Once Standby Mode has been entered using EVO-RC-PLUS Remote Control, it can ALSO be switched off using the On/Off Push Button on the front panel of the EVO Inverter/Charger Unit (See Section 3.4.1.2)
Page 12
Inverter/Charger Manual) will blink once every 5 sec. Red LED marked “FAULT” (13, Fig 2.1 of EVO Inverter/ Charger Manual) and Buzzer will be off 3.4.1.2 Exiting Standby Mode: Using EVO-RC-PLUS: To exit Standby Mode using EVO-RC-PLUS, press the On/Off Key (2, Fig 1.1) • momentarily (0.1 sec). From Front Panel of EVO Inverter/Charger Unit: To exit Standby Mode from the EVO unit, momentarily (0.1...
Page 13
SECTION 3 | Operation CAUTION! The cause of the fault should be removed before the unit is restarted. ATTENTION! La cause du défaut doit être éliminée avant le redémarrage de l'unité. 3.6 OPERATING MODES AND ASSOCIATED LCD DISPLAY SCREENS 3.6.1 General Information When the unit is operating normally, the LCD Screen will display the name of the Operating Mode (See Column 1 of Table 3.1) and values of various associated operating parameters.
Page 15
SECTION 3 | Operation 3.6.2.1 Menu Map for Standby Mode Screens for Models EVO-1212F / 1212F-HW / 1224F / 1224F-HW E V O - 1 2 1 2 F S t a n d b y E V O - 1 2 1 2 F S t a n d b y o u t p u t : 0 .
Page 16
SECTION 3 | Operation 3.6.2.2 Menu Map for Standby Mode Screens for Models (i) EVO-2212 / 3012 / 2224 / 4024 and (ii) EVO- 2212E / 3012E / 2224E / 4024E E V O - 3 0 1 2 S t a n d b y E V O - 3 0 1 2 S t a n d b y o u t p u t :...
Page 17
SECTION 3 | Operation 3.6.2.3 Menu Map for Standby Mode Screens for Model EVO-4248SP E V O - 4 2 4 8 S P S t a n d b y E V O - 4 2 4 8 S P S t a n d b y o u t p u t : E V O...
Page 18
SECTION 3 | Operation 3.6.3 Menu Map for Inverting Mode Screens Menu Maps for the Operating Mode Screens for the "Inverting" Mode are shown as follows: • Section 3.6.3.1: Fig 3.2(a) for Models EVO-1212F / 1212F-HW / 1224F / 1224F-HW (Model No.
Page 19
SECTION 3 | Operation 3.6.3.2 Menu Map for Inverting Mode Screens for Models (i) EVO-2212 / 3012 / 2224 / 4024 and (ii) EVO-2212E / 3012E / 2224E / 4024E E V O - 3 0 1 2 I n v e r t i n g E V O - 3 0 1 2 I n v e r t i n g O u t p u t :...
Page 20
SECTION 3 | Operation 3.6.3.3 Menu Map for Inverting Mode Screens for Model EVO-4248SP E V O - 4 2 4 8 S P I n v e r t i n g E V O - 4 2 4 8 S P I n v e r t i n g E V O V e r :...
Page 21
SECTION 3 | Operation 3.6.4 Menu Map for Charging Mode Screens Menu Maps for the Operating Mode Screens for the "Charging" Mode are shown as follows: • Section 3.6.4.1: Fig 3.3(a) for Models EVO-1212F / 1212F-HW / 1224F / 1224F-HW (Model No.
Page 22
SECTION 3 | Operation 3.6.4.2 Menu Map for Charging Mode Screens for Models (i) EVO-2212 / 3012 / 2224 / 4024 and (ii) EVO-2212E / 3012E / 2224E / 4024E E V O - 3 0 1 2 C h a r g i n g E V O - 3 0 1 2 C h a r g i n g 0 - B u l k...
Page 23
SECTION 3 | Operation 3.6.4.3 Menu Map for Charging Mode Screens for Model EVO-4248SP E V O - 4 2 4 8 S P C h a r g i n g E V O - 4 2 4 8 S P C h a r g i n g 0 - B u l k S t a g e...
Page 24
SECTION 3 | Operation 3.6.4.4 Details of Charging Profiles in Charging Mode Screens Refer to the 2nd Line of the following Charging Mode Screens: • Fig 3.3(a) under Section 3.6.4.1 for Models EVO-1212F / 1212F-HW / 1224F / 1224F-HW • Fig 3.3(b) under Section 3.6.4.2 for Models (i) EVO-2212 / 3012 / 2224 / 4024 and (ii) EVO-2212E / 3012E / 2224E / 4024E •...
Page 25
SECTION 3 | Operation 3.6.5 Menu Map for Power Save Mode Screens Menu Map for the Operating Mode Screens for the "Power Save" Mode are shown as follows: • Section 3.6.5.1: Fig 3.4(a) for Models EVO-1212F / 1212F-HW / 1224F / 1224F-HW (Model No.
Page 26
SECTION 3 | Operation 3.6.5.2 Menu Map for Power Save Mode Screens for Models (i) EVO-2212 / 3012 / 2224 / 4024 and (ii) EVO-2212E / 3012E / 2224E / 4024E E V O - 3 0 1 2 P o w e r S a v e E V O - 3 0 1 2 P o w e r...
Page 27
SECTION 3 | Operation 3.6.5.3 Menu Map for Power Save Mode Screens Model EVO-4248SP Menu Map for the Operating Mode Screens for the "Power Save" Mode are shown at Fig 3.4(c) below: E V O - 4 2 4 8 S P P o w e r S a v e E V O - 4 2 4 8 S P P o w e r S a v e...
Page 28
SECTION 3 | Operation 3.6.6 Menu Maps for On-Line Mode Screens Menu Maps for the On-Line Mode Screens will be similar to the following Menu Map Screens for the default Off-Line Mode except for some changes explained below: Menu Map Screens for Models Menu Map Screens for Models Menu Map Screens for Model EVO-1212F / 1212F-HW / 1224F /...
Page 29
SECTION 3 | Operation 3.6.7 Menu Map for "Chgr Only" (Charger Only) Mode Screens Refer to Section 4.4.2.13.1 for details on "Charger Only" Mode Menu Maps for Operating Mode Screens under this mode for various types of EVO models are shown as follows: •...
Page 30
SECTION 3 | Operation 3.6.7.2 Menu Map for "Chrg Only" (Charger Only) Mode Screens for Models (i) EVO-2212 / 3012 / 2224 / 4024 and (ii) EVO-2212E / 3012E / 2224E / 4024E E V O - 3 0 1 2 C h r g O n l y E V O - 3 0 1 2...
Page 31
SECTION 3 | Operation 3.6.7.3 Menu Map for "Chgr Only" (Charger Only) Mode Screens for Model EVO-4248SP E V O - 4 2 4 8 S P C h r g O n l y E V O - 4 2 4 8 S P C h r g O n l y I n v e r t e r...
Page 32
SECTION 3 | Operation 3.6.8 Menu Maps for Charging Mode Screens When Charging is Switched Off by the Lithium Ion Battery Management System (BMS) For background information, please refer to Sections 4.4.2.22.1 & 4.4.2.22.2 Menu Maps shown in Figs 3.7(a) to 3.7(c) for various EVO models are applicable when parameter "BATTERY TYPE"...
Page 33
SECTION 3 | Operation 3.6.8.2 Menu Map for Charging Mode Screens for Models (i) EVO-2212 / 3012 / 2224 / 4024 and (ii) EVO- 2212E / 3012E / 2224E / 4024E when Charging is Switched Off by Lithium Ion Battery Management System (BMS) Refer to Fig 3.7(b) E V O - 3 0 1 2...
Page 34
SECTION 3 | Operation 3.6.8.3 Menu Map for Charging Mode Screens for Model EVO-4248SP when Charging is Switched Off by the Lithium Ion Battery Management System (BMS) "Chrg-Stop" for 2 sec "by BMS" for 2 sec See NOTE 1 E V O - 4 2 4 8 S P E V O - 4 2 4 8 S P C h a r g e r S t o p...
Page 35
SECTION 3 | Operation 3.6.9 Menu Maps for Inverting Mode Screens When Inverting is Stopped by the Lithium Ion Battery Management System (BMS) For background information, please refer to Sections 4.4.2.22.1 & 4.4.2.22.2 Menu Maps shown in Figs 3.8(a) to 3.8(c) for various EVO models are applicable when parameter "BATTERY TYPE"...
Page 36
SECTION 3 | Operation 3.6.9.2 Menu Map for Inverting Mode Screens for Models (i) EVO-2212 / 3012 / 2224 / 4024 and (ii) EVO- 2212E / 3012E / 2224E / 4024E when Inverting is Stopped by Lithium Ion Battery Management System (BMS) "Inv stop"...
Page 37
SECTION 3 | Operation 3.6.9.3 Menu Map for Inverting Mode Screens for Model EVO-4248SP When Inverting is Stopped by the Lithium Ion Battery Management System (BMS) Refer to Fig 3.8(c) "Inv stop" for 2 sec "Inv stop" for 2 sec "by BMS"...
Page 38
SECTION 4 | Parameter Setup 4.0 "SELECT GROUP" AND "SELECT PARAMETER" MENU MAPS 4.1.1 General Information A number of operating parameters can be programmed to suit the desired operating conditions. The programming parameters have been arranged under 7 groups displayed as "SELECT GROUP" as per details at Table 4.1 below. "Select Group"...
Page 39
SECTION 4 | Parameter Setup 4.1.2 "Select Group" Menu Map Menu Map for "Select Group" is shown at Fig 4.1 below: S e l e c t G r o u p C H A R G E C U R V E Screen No.
Page 40
SECTION 4 | Parameter Setup 4.1.3 "Select Parameter" Menu Map When any of the 8 Parameter Groups from the "Select Group" Menu Map (Fig 4.1) is selected, access is available to the "Select Parameter" Menu Map pertaining to that Group. Location of "Select Parameter" Menu Maps are given in Table 4.2.
Page 41
SECTION 4 | Parameter Setup 4.1.3.1 "Select Parameter" Menu Map for Parameter Group 1: CHARGE CURVE S e l e c t P a r a m e t e r S e l e c t P a r a m e t e r S e l e c t P a r a m e t e r Screen...
Page 42
G E N – No. 9 3. These screens are displayed only when EVO-RC-PLUS is used for models (i) C o a r s e EVO-2212 / 3012 / 2224 / 4024 or (ii)EVO-2212E / 3012E / 2224E / 4024E.
Page 43
SECTION 4 | Parameter Setup 4.1.3.3 "Select Parameter" Menu Map for Parameter Group 5: OTHER FUNCTION S e l e c t P a r a m e t e r S e l e c t P a r a m e t e r O T H E R F U N C T I O N O T H E R...
Page 44
SECTION 4 | Parameter Setup 4.1.3.4 "Select Parameter" Menu Map for Parameter Group 6: RC-PLUS SETTING NOTES: S e l e c t P a r a m e t e r R C - P L U S S E T T I N G 1.
Page 45
SECTION 4 | Parameter Setup INFO There is a 30 second timeout for setting parameters; after 30 seconds the Setting Mode will be cancelled and the display will revert to the Operating Mode Screen associated with current operation. It is highly recommended to set the EVO™ Date and Time (Parameter Group 7, Screen No. 7 in Fig 4.1) as this value is used to record data logging files.
Page 46
SECTION 4 | Parameter Setup 4.2.2 Changing / Entering Parameter Values Each parameter has a programmable range of values specific to the model number of the EVO™. Please refer to Tables 4.3 and 4.6 to 4.10 and Sections 4.10 and 4.11 for details. During parameter programming, the displayed numerical value of the parameter consists of multiple digits that are necessary to display the highest numerical value within the programmable range.
Page 47
SECTION 4 | Parameter Setup 4.3.1 Example of Password Activation and Changing Bulk Current Setting for EVO-1212F / 1212F- HW from Default Value of 20A to 50A Starting from any of the 5 Operating Mode Screens (shown at Figs S e l e c t G r o u p C H A R G E C U R V E...
Page 48
SECTION 4 | Parameter Setup Screen No.1 of the "Select Parameter - CHARGE CURVE" for BULK S e t u p P a r a m e t e r C H A R G E C U R V E CURRENT setting appears as shown on the left..
Page 49
SECTION 4 | Parameter Setup 4.3.2 Disabling Password Protection In the default / factory preset condition, Password Protection is enabled. Password Protection may be disabled, if required. Procedure is given below: 1. Press ENTER Key momentarily from any Operating Mode Screen (see details at Table 3.1) S e l e c t G r o u p •...
Page 50
SECTION 4 | Parameter Setup P a s w o r d c o r r e c t • Flashes twice when Password is correct. (8052) P a s w o r d e r r o r ! ! •...
Page 51
SECTION 4 | Parameter Setup Table 4.3 Group 1 Parameter Set Up: CHARGE CURVE (Refer to Menu Map at Fig 4.2, Section 4.1.3.1) Parameter EVO-1212F EVO-2212 EVO-3012 EVO-1224F EVO-2224 EVO-4024 Setup Parameter EVO-1212F-HW EVO-2212E EVO-3012E EVO-1224F-HW EVO-2224E EVO-4024E EVO-4248SP Screen No. (Column 1) (Column 2) (Column 3)
Page 52
SECTION 4 | Parameter Setup 4.4.2 Description of Parameters under Group 1 - CHARGE CURVE 4.4.2.1 BULK CURRENT (Table 4.3, Screen No. 1) Parameter "BULK CURRENT" sets the maximum charging current during the Bulk Charging Stage. The default value is (a) 20A for EVO-1212F / 1212F-HW, (b) 20A for EVO-1224F / 1224F-HW, (c) 40A for (i) EVO-2212 / EVO-3012 / EVO-2224 / EVO-4024 and (ii) EVO-2212E / EVO-3012E / EVO-2224E / EVO-4024E and (d) 20A for EVO-4248SP.
Page 53
SECTION 4 | Parameter Setup INFO 1. In order to protect against over temperature shut down when operating in higher ambient temperatures, the set value of “BULK CURRENT” is automatically reduced as follows based on temperature sensed at the Power Transformer and at the Heat Sink for the Power Mosfets: a) Models: (i) EVO-2212 / EVO-3012 / EVO-2224 / EVO-4024 and (ii) EVO-2212E / EVO-3012E / EVO-2224E / EVO-4024E Power Transformer Temperature >...
Page 54
SECTION 4 | Parameter Setup 4.4.2.1.1 Programming Steps for Parameter "BULK CURRENT" Any Operating Mode Screen from Fig 3.1 to 3.8 Enter Key Enter Key Enter Key Enter Key E V O - 1 2 1 2 F I n v e r t i n g S e l e c t G r o u p S e l e c t...
Page 55
SECTION 4 | Parameter Setup 4.4.2.4 FLOAT VOLTAGE (Table 4.3, Screen No. 4) This sets the charging voltage in the Constant Voltage Float Stage. 4.4.2.4.1 Programming Steps for Parameter "FLOAT VOLTAGE" Any Operating Mode Screen from Fig 3.1 to 3.8 Enter Key Enter Key Enter Key...
Page 56
SECTION 4 | Parameter Setup 4.4.2.5.1 Programming Steps for Parameter "COMPENSATE" Any Operating Mode Screen from Fig 3.1 to 3.8 Enter Key Enter Key Enter Key Down Key x 4 times E V O - 1 2 1 2 F I n v e r t i n g S e l e c t G r o u p...
Page 57
SECTION 4 | Parameter Setup 4.4.2.7 RESET VOLTAGE (Table 4.3, Screen No. 7) • The inverter will restart when the battery voltage rises to this set value or above after "Battery low voltage!" shutdown occurs (Section 7, Srl. No. 1 of Table 7.1) •...
Page 58
SECTION 4 | Parameter Setup 4.4.2.9 BATT LOW VOLTAGE (Table 4.3, Screen No. 9) This parameter sets the battery low voltage threshold at which the Inverter Section / the complete EVO Inverter/ ™ Charger will be shut down to protect the battery from deep discharge: 4.4.2.9.1 BATTERY LOW VOLTAGE (Value of parameter LV CUT OFF TIME set from 1 to 7200 sec) •...
Page 59
SECTION 4 | Parameter Setup 4.4.2.9.2.3 Automatic switching over to “Charging Mode” has 2 options selectable through programming parameter “INPUT RECOVERY” (Section 4.5.2.11) as follows: a) Option 0=Buffered (Default): Under this option, the unit will initially start in “Inverting Mode”, synchronize with the AC input and then transfer to “Charging Mode”.
Page 60
SECTION 4 | Parameter Setup 4.4.2.11 LV CUT OFF TIME (Table 4.3, Screen No. 11) 4.4.2.11.1 Value of LV CUT OFF TIME: 1 to 7200 sec Even when the Inverter Section is shut down due to “Battery low voltage!” fault condition as described at Section 4.4.2.9, there will still be some power drawn from the battery to keep the other circuitry in the EVO™...
Page 61
SECTION 4 | Parameter Setup TABLE 4.4 CHARGING PROFILE FOR 4-STAGE ADAPTIVE CHARGING FOR EQUALIZATION Options under Programming Charging Stages Battery Type / CAUTIONS! Parameter “EQUALIZE–4 STAGES” 1. Stage 1 – Bulk Stage − Lead Acid: Flooded only EQUALIZE – 4 STAGES •...
Page 62
SECTION 4 | Parameter Setup 4.4.2.12.1 Programming Steps for Parameter "EQUALIZE-4STAGES" Any Operating Mode Screen from Fig 3.1 to 3.8 Enter Key Enter Key Enter Key Down Key x 11 times E V O - 1 2 1 2 F I n v e r t i n g S e l e c t G r o u p...
Page 63
SECTION 4 | Parameter Setup • Standby Mode Screens will be displayed as follows: For EVO-1212F / 1212F-HW / 1224F / 1224F-HW: Menu Map at Fig 3.1(a) For EVO-2212 / 2212E / 3012 / 3012E / 2224 / 2224E / 4024 / 4024E: Menu Map at Fig 3.1(b) For EVO-4248SP: Menu Map at Fig 3.1(c) •...
Page 64
SECTION 4 | Parameter Setup 4.4.2.14.1 Programming Steps for Parameter "ONLINE OPTION" Any Operating Mode Screen from Fig 3.1 to 3.8 Enter Key Enter Key Enter Key Down Key x 13 times E V O - 1 2 1 2 F I n v e r t i n g S e l e c t G r o u p...
Page 65
SECTION 4 | Parameter Setup 1= Option 2: The Transfer Relay will be switched ON (energized) if the battery voltage drops to “LOW VOLT ALARM” (Section • 4.4.2.8), or lower for sustained period = “GS DETECT TIME” (Section 4.4.2.16). The EVO™ will change over to “Charging Mode”...
Page 66
SECTION 4 | Parameter Setup 4.4.2.16.1 Programming Steps for Parameter “GS DETECT TIME” Any Operating Mode Screen from Fig 3.1 to 3.8 Enter Key Enter Key Enter Key Down Key x 15 times E V O - 1 2 1 2 F I n v e r t i n g S e l e c t G r o u p...
Page 67
SECTION 4 | Parameter Setup 4.4.2.18.1 Programming Steps for Parameter “GEN OFF DELAY” Any Operating Mode Screen from Fig 3.1 to 3.8 Enter Key Enter Key Enter Key Down Key x 17 times E V O - 1 2 1 2 F I n v e r t i n g S e l e c t G r o u p...
Page 68
SECTION 4 | Parameter Setup 4.4.2.20.1 Programming Steps for Parameter “ABSORP EXIT AMPS” Any Operating Mode Screen from Fig 3.1 to 3.8 Enter Key Enter Key Enter Key Down Key x 19 times E V O - 1 2 1 2 F I n v e r t i n g S e l e c t G r o u p...
Page 69
SECTION 4 | Parameter Setup TABLE 4.5 PARAMETER "CHARGING PROFILE" - OPTIONS FOR 3-STAGE / 2-STAGE CHARGING Options under Programming Parameter Charging Stages Battery Type “CHARGING PROFILE” 0 = 3 Stage Adaptive 1. Stage 1 – Bulk Stage (For details, see Section 5.7.1.1 of the Owner's Manuals for −...
Page 70
SECTION 4 | Parameter Setup TABLE 4.5 (Continued) PARAMETER "CHARGING PROFILE" - OPTIONS FOR 3-STAGE / 2-STAGE CHARGING Options under Programming Parameter Charging Stages Battery Type “CHARGING PROFILE” 2=3Stage Type2 1. Stage 1 – Bulk Stage (For details, see Section 5.7.1.1 of the Owner's Manual for −...
Page 71
SECTION 4 | Parameter Setup TABLE 4.5 (Continued) PARAMETER "CHARGING PROFILE" - OPTIONS FOR 3-STAGE / 2-STAGE CHARGING Options under Programming Parameter “CHARGING PROFILE” Charging Stages Battery Type 4=2Stage Type2 1. Stage 1 – Bulk Stage (For details, see Section 5.7.1.1 of the Owner's Manuals for −...
Page 72
SECTION 4 | Parameter Setup 4.4.2.22 BATTERY TYPE (Table 4.3, Parameter Setup Screen No. 22) 4.4.2.22.1 General Information Parameter “BATTERY TYPE” is used to change the functionality of RJ-45 Jack marked “Battery Temp. Sensor” on the front panel of EVO (6, Fig 2.1 in the Owner’s Manuals for EVO Inverter/Chargers).
Page 73
SECTION 4 | Parameter Setup b) Wiring Connection: Output from the Solid-State Relay (SSR) Terminals on the Lithium Battery BMS should be wired to the RJ-45 Jack marked “Battery Temp. Sensor” (6, Fig 2.1 in the Owner’s Manuals for EVO Series Inverter/Chargers) as follows: •...
Page 74
SECTION 4 | Parameter Setup 4.4.2.22.3 Programming Steps for Parameter “BATTERY TYPE” Any Operating Mode Screen from Fig 3.1 to 3.8 Enter Key Enter Key Enter Key Down Key x 21 times E V O - 1 2 1 2 F I n v e r t i n g S e l e c t G r o u p...
Page 75
SECTION 4 | Parameter Setup 4.4.2.23.3 Operating Sequence 1) AC input power is available – EVO operates in “Charging Mode” 2) AC input power fails: EVO transfers from “Charging Mode” to “Inverting Mode” 3) The battery continues to get discharged. When battery voltage (i) drops to value equal to / lower than the “BATT LOW VOLTAGE”...
Page 76
SECTION 4 | Parameter Setup 4.4.2.23.4 Programming Steps for Parameter "SAFE CHARGING" Any Operating Mode Screen from Fig 3.1 to 3.8 Enter Key Enter Key Enter Key Down Key x 22 times E V O - 1 2 1 2 F I n v e r t i n g S e l e c t G r o u p...
Page 77
SECTION 4 | Parameter Setup 4.5 GROUP 2 PARAMETER SET UP: INPUT SETTING 4.5.1 Programming Ranges & Default Values of Programming Parameters under Parameter Group 2 – INPUT SETTING Table 4.6 gives details of programming ranges & default values of parameters under Parameter Group No.2 - "INPUT SETTING" . Refer to Fig 4.3 under Section 4.1.3.2 for Menu Map for navigating through various parameters under this Group No.2.
Page 78
SECTION 4 | Parameter Setup NOTES for Table 4.6: DEFAULT FREQ parameter is fixed al 60Hz for EVO-1212F / 1212F-HW / EVO-1224F / 1224F-HW (Option 0=60Hz). If option 1 is entered, the screen line will show "! 1=xxHz" meaning that Option 1 is invalid. Parameter "GEN MAX CURRENT"...
Page 79
SECTION 4 | Parameter Setup If the net AC input current is 1A more than the value of parameter GRID MAX CURRENT for 1 sec, the AC side charging current is clawed back to ensure that GRID MAX CURRENT value is not exceeded. If the value of pass through load current increases to a value of 1A more than the programmed value of GRID MAX CURRENT for 5 sec, input over current protection will be activated based on option to either transfer to Inverting Mode or to shut down the EVO (Refer to details of these 2 options under parameter INPUT OC PROTECT at Section 4.5.2.11):...
Page 80
SECTION 4 | Parameter Setup 4.5.2.3.1 Programming Steps for Parameter "GEN MAX CURRENT" (Only for EVO-2212/ 2212E / 3012 / 3012E / 2224 / 2224E / 4024 / 4024E) Any Operating Mode Screen from Fig 3.1 to 3.8 Enter Key Down Key x 2 times Down Key x 1 time Enter Key...
Page 81
SECTION 4 | Parameter Setup 4.5.2.5.1 Programming Steps for Parameter "HIGH RESET" (i) Down Key x 3 times for EVO-1212F/1212F- HW/1224F/1224F-HW/4248SP (ii) Down Key x 4 times for EVO-2212/2212E/ Any Operating Mode Screen from 3012/3012E/2224/2224E/4024/4024E Fig 3.1 to 3.8 Enter Key Down Key x 1 time Enter Key E V O - 1 2 1 2 F...
Page 82
SECTION 4 | Parameter Setup 4.5.2.7.1 Programming Steps for Parameter "LOW RESET" (i) Down Key x 5 times for EVO-1212F/1212F- HW/1224F/1224F-HW/4248SP (ii) Down Key x 6 times for EVO-2212/2212E/3012/ Any Operating Mode Screen from 3012E/2224/2224E/4024/4024E Fig 3.1 to 3.8 Enter Key Down Key x 1 time Enter Key E V O - 1 2 1 2 F...
Page 83
SECTION 4 | Parameter Setup b) Parameter “SYNCHRONIZATION” set at Option 1= Coarse This setting is selected for EVO-1212F/1212F-HW/1224F/1224F-HW/4248SP if the AC input source is a Generator. As compared to very stable frequency of Grid / Inverter Generator, the frequency of a Generator may vary considerably depending upon the performance of its Speed Governor that compensates for the drop in RPM / frequency when electrical load is switched on / increased or, rise in RPM / frequency when electrical load is decreased /switched off.
Page 84
SECTION 4 | Parameter Setup Parameter “SYNC GRID” is used to program the desired sensitivity of frequency and phase synchronization of the Inverter Section with the AC input voltage fed at the AC Input Terminals marked “GRID” (4,5,6 in Fig 2.3 in Owner’s Manuals for (i) EVO-2212/3012/2224/4024 and (ii) EVO-2212E/3012E/2224E/4024E).
Page 85
SECTION 4 | Parameter Setup 4.5.2.9.1 Programming Steps for Parameter “SYNC GRID” (Only for EVO-2212/ 2212E / 3012 / 3012E / 2224 / 2224E / 4024 / 4024E) Down Key x 7 times for Any Operating Mode Screen from EVO-2212/2212E/3012/3012E Fig 3.1 to 3.8 Enter Key Down Key x 1 time...
Page 86
SECTION 4 | Parameter Setup Parameter SYNC GEN set at Option 1= Coarse (Default) This is the “Default Setting”. This setting is applicable when a Generator is connected to AC Input Terminals marked “GEN” (7,8,9 in Fig 2.3 in Owner’s Manuals for (i) EVO-2212/3012/2224/4024 and (ii) EVO-2212E/3012E/2224E/4024E).
Page 87
SECTION 4 | Parameter Setup 4.5.2.11 INPUT OC PROTECT (Table 4.6: (i) Parameter Setup Screen No.8 under Column 1 for EVO-1212F / 1212F-HW / 1224F / 1224F-HW / 4248SP (ii) Parameter Setup Screen No.10 under Column 2 for EVO-2212/ 2212E / 3012 / 3012E / 2224 / 2224E / 4024 / 4024E) If the net AC input current is 1A more than the value of GRID MAX CURRENT (See Section 4.5.2.2) or GEN MAX CURRENT (See Section 4.5.2.3) for 1 sec, the AC side charging current is clawed back to ensure that GRID MAX CURRENT / GEN MAX CURRENT value is not exceeded.
Page 88
SECTION 4 | Parameter Setup 4.5.2.12 INPUT RECOVERY (Table 4.6: (i) Parameter Screen No. 9 under Column 1 for EVO-1212F / 1212F-HW / 1224F / 1224F-HW / 4248SP (ii) Parameter Setup Screen No. 11 under Column 2 for EVO-2212/ 2212E / 3012 / 3012E / 2224 / 2224E / 4024 / 4024E) This parameter determines how EVO will recover when AC input is made available while in “Battery low voltage!”...
Page 89
SECTION 4 | Parameter Setup Table 4.7 Group 3 Parameter Set Up: INPUT LOW LIMIT (Refer to Menu Map at Fig 4.3, Section 4.1.3.2) Setting range • EVO-1212F/1212F-HW/1224F EVO-4248SP Parameter EVO-2212E / 3012E / 2224E / Parameter /1224F-HW 4024E Setup Screen •EVO-2212 / 3012 / 2224 / 4024 (Column 4) (Column 1)
Page 90
SECTION 4 | Parameter Setup 4.6.2.2.1 Programming Steps for Parameter "CUT OFF VOLT 1" Any Operating Mode Screen from Fig 3.1 to 3.8 Enter Key Down Key x 1 time Down Key x 2 times Enter Key E V O - 1 2 1 2 F I n v e r t i n g S e l e c t G r o u p...
Page 91
SECTION 4 | Parameter Setup 4.6.2.5.1 Programming Steps for Parameter "DETECT TIME 2" Any Operating Mode Screen from Fig 3.1 to 3.8 Enter Key Down Key x 4 times Down Key x 2 times Enter Key E V O - 1 2 1 2 F I n v e r t i n g S e l e c t G r o u p...
Page 92
SECTION 4 | Parameter Setup 4.7 GROUP 4 PARAMETER SET UP: INPUT HIGH LIMIT 4.7.1 Programming Ranges and Default/ Factory Preset Values of Parameters Under Group 4 – INPUT HIGH LIMIT Table 4.8 below gives details of programming ranges and default values of parameters under Parameter Group 4 - INPUT HIGH LIMIT.
Page 93
SECTION 4 | Parameter Setup 4.7.2.2 CUT OFF VOLT 1 (Table 4.8, Parameter Setup Screen No.2) If during "Charging Mode", the AC input voltage rises above "CUT-OFF VOLT 1" for period > "DETECT TIME 1", the EVO™ Inverter/Charger will transfer to "Inverting Mode". 4.7.2.2.1 Programming Steps for Parameter "CUT OFF VOLT 1"...
Page 94
SECTION 4 | Parameter Setup 4.7.2.5 DETECT TIME 2 (Table 4.8, Parameter Setup Screen No.5) This is the time limit in cycles up to which high AC input voltage "CUT-OFF VOLT 2"is allowed. 4.7.2.5.1 Programming Steps for Parameter "DETECT TIME 2" Any Operating Mode Screen from Fig 3.1 to 3.8 Enter Key...
SECTION 4 | Parameter Setup 4.8 GROUP 5 PARAMETER SET UP: OTHER FUNCTIONS 4.8.1 Programming Ranges and Default / Factory Preset Values of Parameters under Group 5 - OTHER FUNCTION Table 4.9 gives details of programming ranges and default values of parameters under Group 5 - OTHER FUNCTION. Refer to Fig 4.4 under Section 4.1.3.3 for Menu Map for navigating through the various parameters under this Group.
Page 96
SECTION 4 | Parameter Setup 4.8.2 Description of Parameters Under Group 5 – OTHER FUNCTION 4.8.2.1 POWER SAVING (Table 4.9, Parameter Setup Screen No.1) INFO For more information on use and application of Power Save Functions, please refer to the following manuals: (i) Sections 4.6.3 and 4.6.4 in Combined Owner's Manual for EVO-1212F / 1212F-HW / 1224F / 1224F-HW (ii) Sections 4.8.3 and 4.8.4 in Combined Owner's Manuals for (i) EVO-2212 / 3012 / 2224 / 4024 and (ii) EVO- 2212E / 3012E / 2224E / 4024E...
Page 97
SECTION 4 | Parameter Setup If the value of power drawn by AC load falls to the "ENTER POINT" value for 5 sec, the unit will enter "Power Save Mode". 4.8.2.2.1 Programming Steps for Parameter "ENTER POINT" Any Operating Mode Screen from Fig 3.1 to 3.8 Enter Key Down Key x 4 times...
Page 98
SECTION 4 | Parameter Setup On/Off Logic Diagram is shown in Fig 4.8 below: Option “0 = Button” External 12VDC signal is fed through Push Button Type of Switch. (Default) • Momentary contact of Push Button > 2 sec will switch EVO Inverter Charger ON 12VDC input After power ON, After power ON,...
Page 99
SECTION 4 | Parameter Setup 4.8.2.4.1 Programming Steps for Parameter "REMOTE SWITCH" Any Operating Mode Screen from Fig 3.1 to 3.8 Enter Key Down Key x 3 times Down Key x 4 times Enter Key E V O - 1 2 1 2 F I n v e r t i n g S e l e c t G r o u p...
Page 100
SECTION 4 | Parameter Setup b) Option "1 = Normal/Fault": When in “Normal” operational state i.e. when not in Fault Mode, the Status Relay will be OFF (de-energized) [(i) “Common” and “NO” contacts will be in open condition and (ii) “Common” and “NC” contacts will be in closed condition].
Page 101
SECTION 4 | Parameter Setup 4.8.2.5.2.1 Option 2 = Generator 0 (This is the Default Option): This Option will start the Generator at “LOW VOLT ALARM” (Section 4.4.2.8) and stop the Generator when the batteries are charged based on Charging Profile selected through programming parameter "CHARGING PROFILE" (Section 4.4.2.21).
Page 102
SECTION 4 | Parameter Setup 4.8.2.5.2.2 Option 3 = Generator 1 This Option will start the Generator at “LOW VOLT ALARM” (Section 4.4.2.8) and stop the Generator when the batteries are charged to the desired programmed level of “RESET VOLTAGE” (Section 4.4.2.7) and stay at this desired level of voltage or higher for the desired programmed time period = “GEN OFF DELAY”...
Page 103
4.8.2.6 COMM ID (Table 4.9, (i) Parameter Setup Screen No. 5 under Column 1 (ii) Parameter Setup Screen No. 6 under Column 2) Parameter "COMM ID" (Communication ID) sets the ID number for the COMM Port and EVO-RC-PLUS Remote Control.
Page 104
SECTION 4 | Parameter Setup Parameter "BUZZER" provides option to switch on/ switch off the buzzer. The default option is "1=On". (i) Down Key x 5 times for EVO-1212F/1212F- 4.8.2.7.1 Programming Steps for Parameter "BUZZER" HW/1224F/1224F-HW (ii) Down Key x 6 times for EVO-2212/2212E/301 Any Operating Mode Screen from 2/3012E/2224/2224E/4024/4024E Fig 3.1 to 3.8...
Page 105
SECTION 4 | Parameter Setup (i) Down Key x 7 times for EVO-1212F/1212F- 4.8.2.9.1 Programming Steps for Parameter "DEFAULT RESET" HW/1224F/1224F-HW (ii) Down Key x 8 times for EVO-2212/2212E/301 Any Operating Mode Screen from 2/3012E/2224/2224E/4024/4024E Fig 3.1 to 3.8 Enter Key Down Key x 4 times Enter Key &...
Page 106
SECTION 4 | Parameter Setup 4.8.2.11 PARAMETER SAVE (Table 4.9, (i) Parameter Setup Screen No. 10 under Column 1 (ii) Parameter Setup Screen No. 11 under Column 2) Save all parameters to SD Card. (See Details at Section 5.4) (i) Down Key x 9 times for EVO-1212F/1212F- 4.8.2.11.1 Programming Steps for Parameter "PARAMETER SAVE"...
Page 107
RC-PLUS SETTING. Refer to Fig 4.5 under Section 4.1.3.4 for Menu Map for navigating through various parameters under this Group 6. These parameters are used to control dimming of LCD back lighting of Remote Control EVO-RC-PLUS. Table 4.10 Group 6 Parameter Set Up: RC-PLUS SETTING (Refer to Menu Map at Fig 4.5, Section 4.1.3.4)
Page 108
4.9.2.1 ACTIVE LCD LIGHT (Table 4.10, Parameter Setup Screen No.1) This parameter determines the level of brightness / dimming of the LCD backlight of Remote Control EVO-RC-PLUS during the "Active" operation of the LCD display (when not in "IDLE LCD LIGHT" mode - see Section 4.9.2.2) The default is option "4=100%"...
Page 109
During the active operation mode of the LCD display, its level of brightness is controlled by parameter "ACTIVE LCD LIGHT" (Section 4.9.2.1). If any key on the EVO-RC-PLUS Remote Control has not been depressed for time set by this parameter i.e. "IDLE LCD TIMER", the backlight of the LCD screen will be dimmed to the level set by parameter "IDLE LCD LIGHT"...
Page 110
SECTION 4 | Parameter Setup 4.11 GROUP 8 PARAMETER SETUP: STOP SD CARD Please refer to Parameter "STOP SD CARD" under Screen No.8 for Group 8 at Fig 4.1 under Section 4.1.2. Please note that this set up is displayed / accessible only when SD Card is inserted in the SD Card Slot (9, Fig 1.1). Set up details are given below: Once SD Card is being used, it should be removed/ejected only after the operation of the Card has been stopped as shown below and message "Please remove SD Card"...
SECTION 5 | SD Card 5.1 SD CARD GENERAL INFORMATION SD Card slot has been provided for using an SD card for (i) data logging and (ii) saving programmed parameters. SD card supports FAT16/FAT32 format up to 32GB in size. When the SD card is inserted, the LCD screen will display the following.
Page 112
With default setting of parameter “DATALOG TIME” (Section 4.8.2.10) set at option “1=1sec”, data logging will commence as soon as the SD Card is inserted in the SD Card Slot in the EVO-RC-PLUS Remote Control (Section 5.2.3). In case parameter “DATALOG TIME” (Section 4.8.2.10) has been set at option “0=Disable”, data logging will NOT commence automatically when the SD Card is inserted in the SD Card Slot in the EVO-RC-PLUS Remote Control.
Page 113
5.2.3 Operating Screens when SD Card is Inserted for Data Logging Data logging will be carried out automatically as soon as the SD Card is inserted in the SD Card Slot of EVO-RC-PLUS. [Provided parameter “DATALOG TIME” (Section 4.8.2.10) has NOT been set to “0 = Disable”)].
Page 114
SECTION 5 | SD Card 5.2.4 Disabling Data Logging In the factory default condition, data logging has been enabled at 1 sec recording interval [Parameter "DATALOG TIME" (Section 4.8.2.10) has been set to option "1=1 sec"]. Hence, data logging will commence as soon as SD Card is inserted. To disable data logging, parameter "DATALOG TIME"...
Page 115
SECTION 5 | SD Card TABLE 5.2 Example of Data Log Text File "0716007.txt" for Model No. EVO-4024 as seen through Text Editor "Notepad" 5.3.2.1 Follow procedure given below to open Data Log Files in Microsoft Excel (Version used is 2016): •...
Page 116
SECTION 5 | SD Card • Click "Open" Button (Bottom right corner of Fig 5.4). • "Text Import Wizard – Step 1 of 3" will be shown (Fig 5.5). Choose "Delimited"File Type". Fig 5.5 Screen showing Step 1 of 3 of "Text Import Wizard" in Excel •...
Page 117
SECTION 5 | SD Card • Data as in Fig 5.7 will be displayed on your Worksheet, with the Log Data stored in Columns and Rows. Fig 5.7 Screen showing Data Log Work Sheet in Excel 5.4 SAVING / UPLOADING PROGRAMMED PARAMETERS 5.4.1 Saving Programmed Parameters All the programmed parameters can be saved on an SD Card (FAT 16 / FAT 32 Format, up to 32 GB capacity).
Page 118
SECTION 5 | SD Card 5.4.2 Uploading Saved Parameters If there is a “xxxx_yyy.cfg” file in the SD card with stored programmed parameters, then on inserting the card, the Remote Control will ask to upload the Config File. Press Enter Button to confirm or Back Button to cancel. U p l o a d c o n f ? •...
Beep once in 1 sec interval Power saving Blink once in 3 sec interval Standby Blink once in 5 sec interval Fault NOTE: Buzzer is available only in EVO™ Inverter/Charger. There is no buzzer in Remote Control EVO-RC-PLUS. SAMLEX AMERICA INC. | 119...
TABLE 7.1 FAULT MESSAGES AND TROUBLESHOOTING GUIDE NOTES: 1. Please see Table 6.1 for LED indications in EVO-RC-PLUS and buzzer indications in EVO™ Inverter/Charger 2. Buzzer is available only in EVO™ Inverter/Charger. There is no buzzer in Remote Control EVO-RC-PLUS Srl.
Page 121
SECTION 7 | Fault Messages and Troubleshooting Guide Srl. Fault Message Symptoms and Troubleshooting • EVO™ is in FAULT MODE because the battery voltage has dropped momentarily for 1 ms to (i) 9V or below for EVO-1212F/1212F-HW/2212/2212E/ 3012/3012E or, (ii) 18V or below for EVO- 1224F/1224F-HW/2224/2224E/4024/4024E or (iii) 36V or below for EVO-4248SP.
Page 122
SECTION 7 | Fault Messages and Troubleshooting Guide Srl. Fault Message Symptoms and Troubleshooting EVO™ Inverter/Charger is in FAULT MODE because the battery voltage has risen to the set upper threshold of “BATT OVER VOLTAGE” (Section 4.4.2.6) (a) AC input is not available and EVO™ Inverter/Charger is operating in Inverting Mode: •...
Page 123
SECTION 7 | Fault Messages and Troubleshooting Guide Srl. Fault Message Symptoms and Troubleshooting EVO™ Inverter/Charger is in FAULT MODE because of overload conditions in Inverting Mode: • There will be no AC output because the Inverter Section will be switched OFF. The Blue LED marked “Status”...
Page 124
SECTION 7 | Fault Messages and Troubleshooting Guide Srl. Fault Message Symptoms and Troubleshooting EVO™ Inverter/Charger is in FAULT MODE because the main Bidirectional Transformer in the EVO™ Inverter/Charger has overheated to 150°C • The Blue LED marked “Status” will be switched OFF and the Red LED marked “Fault” will be steady ON.
Warranty 3 YEAR LIMITED WARRANTY EVO-RC-PLUS manufactured by Samlex America, Inc. (the “Warrantor“) is warranted to be free from defects in workmanship and materials under normal use and service. The warranty period is 3 years for the United States and Canada, and is in effect from the date of purchase by the user (the “Purchaser“).