SECTION 4 |
4.4.2.7 RESET VOLTAGE (Table 4.3, Screen No. 7)
The inverter will restart when the battery voltage rises to this set value or above after "Battery low voltage!"
shutdown occurs (Section 7, Srl. No. 1 of Table 7.1)
If automatic starting / stopping of Generator is used with RELAY FUNCTION set at "3= Generator 1" (Section
4.8.2.5.2.2), the Relay will turn off when the battery voltage remains at this value or higher for time period equal
to "GEN OFF DELAY" (Section 4.4.2.18). Turning Off the Relay will automatically stop the Generator [Refer to
Section 4.8.2.5.2.2 for details].
4.4.2.7.1 Programming Steps for Parameter "RESET VOLTAGE"
Any Operating Mode Screen from
Fig 3.1 to 3.8
E V O - 1 2 1 2 F
I n v e r t i n g
A C
o u t p u t :
1 2 0 . 0 V
< 0 . 1 0 A
6 0 . 0 0 H z
[Above screen is Screen 1 of Fig 3.2(a)]
4.4.2.8 LOW VOLT ALARM (Table 4.3, Screen No. 8)
When inverting, if battery voltage is under the set value of "LOW VOLTAGE ALARM", the Red LED marked
"Fault" flashes once per second. The buzzer in EVO™ Inverter/Charger will beep once per second.
If automatic starting / stopping of Generator is used with "RELAY FUNCTION" programmed at "2=Generator 0"
(Section 4.8.2.5.2.1) or "3= Generator 1" (Section 4.8.2.5.2.2) or "4= Generator 2" (Section 4.8.2.5.2.3), the
Relay will turn ON if the battery voltage dips to the value of "LOW VOLTAGE ALARM" and remains at this level
or lower for time period equal to the value of "GS DETECT TIME" (Section 4.4.2.16). Turning ON of the relay will
automatically start the Generator (Refer to Sections 4.8.2.5.2.1 to 3 for details).
If parameter "MODE" is programmed at "1= Online" (see Section 4.4.2.13) and parameter "ONLINE OPTION"
is programmed at 0= Option 1" or "1 = Option 2" (see Section 4.4.2.14), the Transfer Relay will be switched ON
if the battery voltage drops to the programmed value of "LOW VOLTAGE ALARM" or lower for a period equal
to the parameter "GS DETECT TIME" (Section 4.4.2.16). Switching ON of the Transfer Relay will initiate battery
charging and AC pass-through (See Section 4.4.2.14 for details).
4.4.2.8.1 Programming Steps for Parameter "LOW VOLT ALARM"
Any Operating Mode Screen from
Fig 3.1 to 3.8
E V O - 1 2 1 2 F
I n v e r t i n g
A C
o u t p u t :
1 2 0 . 0 V
< 0 . 1 0 A
6 0 . 0 0 H z
[Above screen is Screen 1 of Fig 3.2(a)]
Parameter Setup
Enter Key
S e l e c t
G r o u p
*
C H A R G E
C U R V E
ð
P a s s w o r d
k e y
0 0 0 0
Password 8052
See Section 4.3.1
Enter Key
S e l e c t
G r o u p
*
C H A R G E
C U R V E
ð
P a s s w o r d
k e y
0 0 0 0
Password 8052
See Section 4.3.1
Enter Key
S e l e c t
P a r a m e t e r
C H A R G E
ð
*
B U L K
C U R R E N T
2 0 A
Enter Key
S e l e c t
P a r a m e t e r
i n
C H A R G E
ð
*
R E S E T
V O L T A G E
1 4 . 0 0 V
See Table 4.3, Parameter Setup
Screen No. 7 for
programmable range
Enter Key
S e l e c t
P a r a m e t e r
C H A R G E
ð
*
B U L K
C U R R E N T
2 0 A
Enter Key
S e l e c t
P a r a m e t e r
i n
C H A R G E
ð
*
L O
V O L T
W
1 1 . 0 0 V
See Table 4.3, Parameter Setup
Screen No. 8 for
programmable range
Down Key x 6 times
S e l e c t
C U R V E
C H A R G E
ð
*
R E S E T
C U R V E
Down Key x 7 times
S e l e c t
C U R V E
C H A R G E
ð
*
L O
W
C U R V E
A L A R M
SAMLEX AMERICA INC. | 57
Enter Key
P a r a m e t e r
C U R V E
ð
V O L T A G E
1 4 . 0 0 V
Enter Key
P a r a m e t e r
C U R V E
ð
V O L T
A L A R M
1 1 . 0 0 V