SECTION 4 |
Table 4.7 Group 3 Parameter Set Up: INPUT LOW LIMIT (Refer to Menu Map at Fig 4.3, Section 4.1.3.2)
Parameter
Parameter
Setup Screen
No.
(Column 1)
(Column 2)
1
RESET VOLTAGE
2
CUT OFF VOLT 1
3
DETECT TIME 1
4
CUT OFF VOLT 2
5
DETECT TIME 2
6
CUT OFF VOLT 3
7
DETECT TIME 3
4.6.2 Description of Parameters Under Group 3 – INPUT LOW LIMIT
4.6.2.1 RESET VOLTAGE (Table 4.7, Parameter Setup Screen No.1)
This is the reset voltage at which the unit will revert to "Charging Mode" after it has switched over to "Inverting Mode"
due to input voltage falling to "CUT-OFF VOLT 1 / CUT-OFF VOLT 2 / CUT-OFF VOLT3".
4.6.2.1.1 Programming Steps for Parameter "RESET VOLTAGE"
Any Operating Mode Screen from
Fig 3.1 to 3.8
E V O - 1 2 1 2 F
I n v e r t i n g
A C
o u t p u t :
1 2 0 . 0 V
< 0 . 1 0 A
6 0 . 0 0 H z
[Above screen is Screen 1 of Fig 3.2(a)]
4.6.2.2 CUT OFF VOLT 1 (Table 4.7, Parameter Setup Screen No.2)
If during "Charging Mode", the AC input voltage falls below "CUT-OFF VOLT 1" for period > "DETECT TIME 1", the
EVO™ Inverter/Charger will transfer to Inverting Mode from "Charging Mode".
Parameter Setup
• EVO-1212F/1212F-HW/1224F
/1224F-HW
•EVO-2212 / 3012 / 2224 / 4024
(Column 3)
60.0 - 120.0V
(Default:105.0V)
60.0 - 120.0V
(Default: 100.0V)
0 - 2000 cycles
(Default: 300 cycles)
60.0 - 120.0V
(Default: 95.0V)
0 - 2000 cycles
(Default: 60 cycles)
60.0 - 120.0V
(Default: 90.0V)
0 - 2000 cycles
(Default: 1 cycle)
Enter Key
S e l e c t
G r o u p
*
C H A R G E
C U R V E
ð
P a s s w o r d
k e y
0 0 0 0
Password 8052
See Section 4.3.1
Setting range
EVO-2212E / 3012E / 2224E /
Down Key x 2 times
S e l e c t
P a r a m e t e r
*
I N P U T
L O
W
ð
Enter Key
i n
S e l e c t
P a r a m e t e r
I N P U T
L O
W
ð
*
R E S E T
V O L T A G E
1 0 5 . 0 V
See Table 4.7, Parameter Setup
Screen No. 1
for programmable range
4024E
(Column 4)
140.0 - 200.0V
(Default:190.0V)
140.0 - 200.0V
(Default:180.0V)
0 - 2000 cycles
(Default: 300 cycles)
140.0 - 200.0V
(Default:170.0V)
0 - 2000 cycles
(Default: 60 cycles)
140.0 - 200.0V
(Default:160.0V)
0 - 2000 cycles
(Default: 1 cycle)
Enter Key
S e l e c t
L I M I T
I N P U T
ð
*
R E S E T
1 0 5 . 0 V
L I M I T
SAMLEX AMERICA INC. | 89
EVO-4248SP
(Column 5)
60.0 - 200.0V
(Default:195.0V)
60.0 - 200.0V
(Default:185.0V)
0 - 2000 cycles
(Default: 300 cycles)
60.0 - 200.0V
(Default:175.0V)
0 - 2000 cycles
(Default: 60 cycles)
60.0 - 200.0V
(Default:165.0V)
0 - 2000 cycles
(Default: 1 cycle)
Enter Key
P a r a m e t e r
L O
L I M I T
W
ð
V O L T A G E