SECTION 4 |
4.4.2.18.1 Programming Steps for Parameter "GEN OFF DELAY"
Any Operating Mode Screen from
Fig 3.1 to 3.8
E V O - 1 2 1 2 F
I n v e r t i n g
A C
o u t p u t :
1 2 0 . 0 V
< 0 . 1 0 A
6 0 . 0 0 H z
[Above screen is Screen 1 of Fig 3.2(a)]
4.4.2.19 ABSORP TIME (Table 4.3, Parameter Setup Screen No. 19)
Parameter "ABSORP TIME" is used to set the time the charger will remain in Absorption Stage when the following
options for programming parameter "Charging Profile" (See Section 4.4.2.21) are selected:
1=3 Stage Type 1
3=2 Stage Type 1
i
INFO
When using Charging Profile options (i) "1=3Stage Type 1" or (ii) "3=2Stage Type1, a nearly fully charged
battery may be overcharged / boil if the programmed duration of "ABSORP TIME" is excessively long. Care
should be taken to determine the time the battery is required to remain in Absorption Stage ("ABSORP TIME")
based on the application and then, set programming parameter "ABSORP TIME" accordingly
Programmable range is 0 – 600 min. Default value is 60 min
4.4.2.19.1 Programming Steps for Parameter "ABSORP TIME"
Any Operating Mode Screen from
Fig 3.1 to 3.8
E V O - 1 2 1 2 F
I n v e r t i n g
A C
o u t p u t :
1 2 0 . 0 V
< 0 . 1 0 A
6 0 . 0 0 H z
[Above screen is Screen 1 of Fig 3.2(a)]
4.4.2.20 ABSORP EXIT AMPS (Table 4.3, Parameter Setup Screen No. 20)
Parameter "ABSORP EXIT AMPS" is used to set the value of the charging current at which the charger will exit Absorption
Stage and transition to Float Stage when the following option for programming parameter "Charging Profile" (See
Section 4.4.2.21) is selected"
2=3 Stage Type 2
Programmable range is 0 – 20A. Default value is 4A
Parameter Setup
Enter Key
S e l e c t
G r o u p
*
C H A R G E
C U R V E
ð
P a s s w o r d
k e y
0 0 0 0
Password 8052
See Section 4.3.1
Enter Key
S e l e c t
G r o u p
*
C H A R G E
C U R V E
ð
P a s s w o r d
k e y
0 0 0 0
Password 8052
See Section 4.3.1
Enter Key
S e l e c t
P a r a m e t e r
C H A R G E
ð
*
B U L K
C U R R E N T
2 0 A
Enter Key
S e l e c t
P a r a m e t e r
i n
C H A R G E
ð
*
G E N
O F F
6 0
m i n
See Table 4.3, Parameter Setup
Screen No. 18 for
programmable range
Enter Key
S e l e c t
P a r a m e t e r
C H A R G E
ð
*
B U L K
C U R R E N T
2 0 A
Enter Key
i n
S e l e c t
P a r a m e t e r
C H A R G E
ð
*
A B S O R P
6 0
m i n
See Table 4.3, Parameter Setup
Screen No. 19 for
programmable range
Down Key x 17 times
S e l e c t
C U R V E
C H A R G E
ð
*
G E N
C U R V E
D E L A Y
Down Key x 18 times
S e l e c t
C U R V E
C H A R G E
ð
*
A B S O R P
C U R V E
T I M E
SAMLEX AMERICA INC. | 67
Enter Key
P a r a m e t e r
C U R V E
ð
O F F
D E L A Y
6 0
m i n
Enter Key
P a r a m e t e r
C U R V E
ð
T I M E
6 0
m i n