SECTION 4 |
4.5.2.12 INPUT RECOVERY
(Table 4.6: (i) Parameter Screen No. 9 under Column 1 for EVO-1212F / 1212F-HW / 1224F / 1224F-HW / 4248SP
(ii) Parameter Setup Screen No. 11 under Column 2 for EVO-2212/ 2212E / 3012 / 3012E /
2224 / 2224E / 4024 / 4024E)
This parameter determines how EVO
"Battery ultra low voltage!" fault conditions (Srl. Nos. 1 and 2 respectively of TABLE 7.1). The following 2 options are
available under this parameter:
• Option "0=Buffered" (This is the default option)
• Option "1=Direct"
is in "Battery low voltage!" condition (Section 7, Srl 1 of TABLE 7) or in "Battery ultra low voltage!"
When the EVO
TM
condition (Section 7, Srl. 2 of TABLE 7.1) and if AC input is made available before expiry of time set by parameter "LV
CUT OFF TIME" (Section 4.4.2.11), the "Battery low voltage!" / "Battery ultra low voltage!" fault conditions will be
cleared and EVO
Inverter/Charger will recover based on the following 2 options:
TM
a) Option 0=Buffered (Default): Under this option, the unit will initially start in "Inverting Mode",
synchronize with the AC input and then transfer to "Charging Mode". However, if a user programs the
value of "BATTERY LOW VOLTAGE" very close to the "Battery ultra low voltage!" fault threshold of (i) 9V
for 1 ms for EVO-1212F/1212F-HW/2212/3012 or, (ii)18V for 1 ms for EVO-1224F/1224F-HW/2224/4024
or, (iii) 36V for 1ms for EVO-4248SP (Table 7.1), a larger load / larger starting surge on the inverter may
drag the battery voltage to 9V / 18V / 36V or below for 1 ms and trigger "Battery ultra low voltage!" fault.
Under this condition, the user may change to Option 1=Direct
b) Option 1=Direct: Under this option, the unit will directly start in "Charging Mode"
4.5.2.12.1 Programming Steps for Parameter "INPUT RECOVERY"
Any Operating Mode Screen from
Fig 3.1 to 3.8
E V O - 1 2 1 2 F
I n v e r t i n g
A C
o u t p u t :
1 2 0 . 0 V
< 0 . 1 0 A
6 0 . 0 0 H z
[Above screen is Screen 1 of Fig 3.2(a)]
4.6 GROUP 3 PARAMETER SET UP: INPUT LOW LIMIT
4.6.1 Programming Ranges and Default / Factory Preset Values of Parameters under Group 3 -
INPUT LOW LIMIT
Table 4.7 gives details of programming ranges and default values of parameters under Group 3 - INPUT LOW LIMIT.
Refer to Fig 4.3 under Section 4.1.3.2 for Menu Map for navigating through the various parameters under this Group 3.
88 | SAMLEX AMERICA INC.
Parameter Setup
will recover when AC input is made available while in "Battery low voltage!" or
TM
Enter Key
S e l e c t
G r o u p
*
C H A R G E
C U R V E
ð
S e l e c t
P a r a m e t e r
I N P U T
S E T T I N G
*
I N P U T
R E C O V E R Y
0 = B u f f e r e d
Down Key x 1 time
S e l e c t
P a r a m e t e r
*
I N P U T
S E T T I N G
ð
Enter Key
P a s s w o r d
k e y
0 0 0 0
ð
Password 8052
See Section 4.3.1
(i) Down Key x 8 times for EVO-1212F/1212F-
HW/1224F/1224F-HW/4248SP
(ii) Down Key x 10 times for EVO-2212/2212E/
3012/3012E/2224/2224E/4024/4024
Enter Key
S e l e c t
P a r a m e t e r
I N P U T
S E T T I N G
ð
*
D E F A U L T
0 = 6 0 H z
Enter Key
i n
S e l e c t
P a r a m e t e r
I N P U T
S E T T I N G
ð
*
I N P U T
R E C O V E R Y
0 = B u f f e r e d
For programmable options, see Table 4.6:
(i) Parameter Setup Screen No. 9 under Column 1 for
EVO- 1212F/1212F-HW/1224F/1224F-HW/4248SP
(ii) Parameter Setup Screen No. 11 under Column 2 for
EVO-2212/2212E/3012/3012E/2224/2224E/4024/4024E