Omron TJ2-MC02 Hardware Reference Manual page 150

Trajexia machine control system
Table of Contents

Advertisement

Hardware reference
Configuration Errors
If the Option Board is correctly configured, the RUN indicator will be ON and
the ERR indicator OFF. The table below shows the indicator and display
patterns caused by configuration errors.
Display &
Possible Cause(s)
Indicators
One of the configuration parame-
ters P160 - P179 has been
rejected by the Inverter.
RUN
ERR
RX
TX
Your Inverter version has not
been properly verified with this
version of the Option Board (The
MECHATROLINK node address
ERR
TX
RUN
RX
in the Inverter is invalid or
absent).
Your Inverter version has not
been properly verified with this
version of the Option Board
(Some Option Board parameters
RUN
ERR
RX
TX
in the Inverter are invalid or
absent).
HARDWARE REFERENCE MANUAL
Corrective Action
I/O mapping is not supported by this
option board. Make sure parameters
P160 - P179 are set to 0.
Reset the Inverter to factory defaults. If
the problem persists, contact your local
OMRON representative for assistance.
Reset the Inverter to factory defaults. If
the problem persists, contact your local
OMRON representative for assistance.