Hardware reference
Configuring the Option Board
All Option Board parameters are stored in the RX Inverter. This allows for
easy replacement of the Option Board without the need to re-configure.
After connecting the Option Board to an RX Inverter for the first time
however, proceed with the following steps:
Step 1
It is recommended to set C102 = 3 to prevent the Inverter reset input and
Stop/reset button from interfering with Option Board during operation
(Setting C102 to another value causes the Option Board to reset when a trip
condition is cleared). Use the Inverter keypad to set C102 to 3.
Param Description
Setting
C102
Reset mode selection Recommended to set to 3 (Reset mode selection
resets trip only, not Option Board)
Step 2
Inverter registers P195 and P196 configure the MECHATROLINK-II
network-related parameters. Adjust these to configure the frame length and
node address.
Param Description
Setting
P195
MECHATROLINK
0: 32 bytes (default after inverter reset)
frame length
1: 17 bytes
P196
MECHATROLINK
21h to 3Eh
node address