7.2 Indication of the Operation Modes
Operation
Mode
Normal
The POWER SUPPLy 230V green
LED lights on the front panel.
Mode
• The two red FIRE LEDs light up si-
multaneously - the FIRE LED and the
FIRE
zone/zones LED (also in red) where the
A FIRE relay is
alarm occurred.
activated.
• The LEDs will remain lit even after the
• The GENERAL FAULT yellow LED
FAULT
and the fault LED according to the Ta-
A FAULT relay
ble in item 7.1 light up simultaneously.
is activated.
TEST
• The two yellow LEDs blink simultane-
Tests the sys-
ously - the TEST LED and the zone
tem for proper
LED (also in yellow, 2 blinks per sec-
operational
ond) where the test is conducted.
efficiency
• The ENABLE/DISABLE yellow LED
is lit on.
DISABLE
• The respective zone LEDs light up in
Disabled
yellow to indicate disabled zones.
zones and/or
• The yellow SOUNDER FAULT/DISA-
sounders.
BLE LED lights up to indicate disabled
sounders.
LED Indication
button has been pressed.
MAG8Plus - Installation and Operation Manual
Sound Signalization
-
• The sounders are activated.
They can be disabled by
pressing the
button and can then be
enabled by pressing the
.
• The internal buzzer is acti-
vated. It is disabled by press-
ing the
• The internal buzzer is acti-
vated. It is disabled by press-
ing the
• The internal buzzer is acti-
vated. It is disabled by press-
ing the
-
button.
button.
button.
27