Repeater Panel - Teletek electronics MAG8Plus Installation And Operation Manual

Fire control panel
Table of Contents

Advertisement

4.2 Repeater Panel

A second MAG8Plus can be connected to the MAG8Plus Fire Alarm panel as Slave. The
function of the Slave is to double the light and sound indication and the button control of
the first panel at a distance up to 1000 m. For the purpose, to both of the panels have to
be assigned specific priorities: The first fire alarm panel shall be the system Master and
the second - Slave.
The Master panel is configured by setting a jumper on the Master position of the main
module, and the Slave - with a jumper on the Slave position (see Figure 10).
Figure 20 shows the connection between the Master and Slave MAG8Plus panels.
When adding a repeater panel in the fire system:
• Turn off the main and the stand-by power supplies.
• Connect the repeater to the first MAG8Plus - see Figures 20, 21 and 22.
• Set a jumper on the Master position of the main panel - see Figures 10 and 20.
• Set a jumper on the Slave position of the second panel - see Figures 10 and 20.
• Turn on the main and the stand-by power supplies of the Slave panel.
• Turn on the main and the stand-by power supplies of the Master panel.
Master
Panel
MAG8Plus
Master
Panel
MAG8Plus
Master
Panel
MAG8Plus
Connecting of Repeater Panel
MAG8Plus - Installation and Operation Manual
Figure 20.
Connecting between
Repeater and Master
Panel.
Figure 21.
Connecting between
one Relay Module,
Repeater and Master
Panel.
Figure 22.
Connecting between
two Relay Modules,
Repeater and Master
Panel.