Mag8 Operation Modes; Led Indication For The Status Of The Zones (1-8); Led Indication For The Technical Faults In The System - Teletek electronics MAG8P Installation And Operation Manual

Fire control panel
Table of Contents

Advertisement

1.1 MAG8 Operation Modes:

MODE
Normal
• Only the "POWER SUPPLy 230V" green LED is illuminated.
• The "FIRE" red LED and the zone red LED will flash together on receipt
of a FIRE condition and become steady after the "SILENCE ALARM"
button is pressed.
Fire
• An internal buzzer will operate until silenced.
• The external sounders will operate.
• The FIRE relay will energize.
• The "GENERAL FAULT" yellow LED will illuminate together with a zone
yellow LED or any of the FAULTS LED.
Fault
• An internal buzzer will sound.
• The FAULT relay will de-energize.

1.2 LED indication for the status of the zones (1-8):

ZONE LED
Red
Fire in the zone.
Technical fault in the zone - open or short circuit; detector removed
Yellow
from its base.
Zone test - the LED is flashing during the test procedure.

1.3 LED indication for the technical faults in the system:

FAULT
sounder 1
sounder 2
+24v DC Overload Overload of "+24" VDC power supply.
+24v DC Failed
Battery Low
Battery Lost
AC
Charger
AUX
Earth
Repeater
Fire Control Panel MAG8 - Installation and Operation Manual
Sounder Circuit One fault - open or short circuit, reverse
connected sounder, or bad sounder parameters.
Sounder Circuit Two fault - open or short circuit, reverse
connected sounder, or bad sounder parameters.
Absence of "+24" VDC power supply.
Low battery condition - the LED lights on;
Broken battery (high battery resistance) - the LED is blinking.
Battery loss.
Mains Supply loss.
Battery charger fault.
Auxiliary supply fault.
Short circuit to earth.
Repeater fault or missing.
Indication
Indication
Fault description
5