Teletek electronics MAG8P Installation And Operation Manual

Teletek electronics MAG8P Installation And Operation Manual

Fire control panel

Advertisement

Quick Links

MAG8
FIRE CONTROL PANEL
English
Installation and Operation Manual
C1293

Advertisement

Table of Contents
loading

Summary of Contents for Teletek electronics MAG8P

  • Page 1 MAG8 FIRE CONTROL PANEL English Installation and Operation Manual C1293...
  • Page 2: Table Of Contents

    FIRE ALARM EvENT LOG ..................19 sPARE PARTs KIT ....................19 DoP No: 074 1293 - CPR - 0542 Teletek Electronics JSC, 14 Srebarna Str., 1407 Sofia, Bulgaria EN 54-2:1997; EN 54-2:1997/AC:1999; EN 54-2:1997/A1:2006; EN 54-4:1997; EN 54-4:1997/AC:1999; EN 54-4:1997/A1:2002; EN 54-4:1997/A2:2006 MAG8 Intended for use in fire detection and fire alarm systems in and around buildings.
  • Page 3: Guarantee

    The manufacturer shall not accept any product, of which no prior notice has been received via the RAN form at: http://www.teletek-electronics.com/en/ran-form The setup and programming included in the technical documentation shall not be regarded as defects. Teletek Electronics bears no responsibility for the loss of programming information in the device being serviced.
  • Page 4: Using The Mag8 Controls

    Fire Control Panel MAG8 - Installation and Operation Manual 1. Using the MAG8 Controls LED indication for the status of the zones - see item 1.2. LED indication for the technical faults in the system - see item 1.3. This indication is not visible from the user.
  • Page 5: Mag8 Operation Modes

    Fire Control Panel MAG8 - Installation and Operation Manual 1.1 MAG8 Operation Modes: MODE Indication Normal • Only the “POWER SUPPLy 230V” green LED is illuminated. • The “FIRE” red LED and the zone red LED will flash together on receipt of a FIRE condition and become steady after the “SILENCE ALARM”...
  • Page 6: Led Indication For The System Status

    Fire Control Panel MAG8 - Installation and Operation Manual 1.4 LED indication for the system status: Indication FIRE Fire in the premises. (red) GENERAL FAULT Main Fault indicator. (yellow) OUTPUT DELAY Lights permanently at programmed outputs time delay (yellow) (a jumper is set on the TIME DELAY terminal). µP FAULT Processor break down.
  • Page 7: Installing The Mag8 Panel

    Fire Control Panel MAG8 - Installation and Operation Manual 2. Installing the MAG8 Panel • Choose the best location for the panel position, with an ambient temperature between -5°C and 40°C, away from heating sources, environmental dust and potential water ingress.
  • Page 8: Initial Power-Up Of Mag8 Panel

    Fire Control Panel MAG8 - Installation and Operation Manual 3. Initial Power-up of MAG8 Panel ATTENTION: It has been assumed that prior to making the connection at the panel, the integrity of the system ALL wiring has been comprehensively tested, including insulation to earth. •...
  • Page 9: Connecting The Sounders Circuits

    Fire Control Panel MAG8 - Installation and Operation Manual • Operate ALL detection devices applicable to this zone, to ensure correct receipt of a fire signal and the correct operation of the panel controls. Refer to the User Instructions on the inside of the panel.
  • Page 10: Class Change Function

    Fire Control Panel MAG8 - Installation and Operation Manual 7. Class Change Function To use the class change function connect the terminals of a switch with normally open contacts to the CC (Class Change) clamps of the main module terminal. The working mode of the sounders will be: - when the switch is pressed - one second sounder on, one second sounder off;...
  • Page 11: Programming Wireless Receiver Mode

    Fire Control Panel MAG8 - Installation and Operation Manual 12. Programming Wireless Receiver Mode In order to program the Wireless Receiver mode: • Set a jumper on the Wireless position of the main module. • Press the “ RESET” button to introduce changes. 13.
  • Page 12: Instant Action Mode

    Fire Control Panel MAG8 - Installation and Operation Manual Attention: The fire alarm panel MAG8 is capable to distinguish the activation of automatic fire alarm detector and call point. In case of call point activation, the programmed DOUBLE Action mode will be ignored and the sounders will be activated immediately. In order to program the MAG8 panel for Double Action mode: •...
  • Page 13: Operating Instructions

    Fire Control Panel MAG8 - Installation and Operation Manual 16. Operating Instructions 16.1 sound signalization signal Description After pressing the “ RESET” button and upon the initial start-up of short beeps the panel. Fire and/ or Fault operating mode. The signal can be stopped by Continuous pressing the “...
  • Page 14 Fire Control Panel MAG8 - Installation and Operation Manual sounders Enable / Disable A sound signalization is activated at every service Mode entering. The signalization is off by pressing “ sILENCE BUZZER” button. To disable the sounders: DISABLE/ ENABLE LED blinks. The ZONE 1 yellow LED blinks if ZONE 1 is en- •...
  • Page 15 Fire Control Panel MAG8 - Installation and Operation Manual “One Man” Test The “One Man” Test mode gives the installer the possibility to test the efficiency of the system - whether the detectors react to smoke, heat, etc. To “One Man” Test a zone: TEST LED will start blinking.
  • Page 16: Connection Diagram

    Fire Control Panel MAG8 - Installation and Operation Manual 17. Connection Diagram...
  • Page 17: Technical Specifications

    Fire Control Panel MAG8 - Installation and Operation Manual 18. Technical Specifications Zones 8 fixed zones Maximum number of detectors per zone Up to 32 devices* Including 20 (or 32 SensoMAG) automatic detectors and/ or manual call points. Thresholds for zone conditions •...
  • Page 18: Fire Alarm Record

    Fire Control Panel MAG8 - Installation and Operation Manual FIRE ALARM RECORD Installation Address: ....................... Contact Person: ....................... Telephone: ....................... Fax: ....................... Date Completed: ....................... Commissioned By: ....................... Contract Reference: ....................... Service Intervals: Monthly / Quarterly / Half yearly / Annually sOUNDERs DETECTOR TYPE and QUANTITY (Zone Quantity and...
  • Page 19: Fire Alarm Event Log

    Fire Control Panel MAG8 - Installation and Operation Manual FIRE ALARM EvENT LOG FAULT FIRE ZONE ACTION DATE TIME yes/no and Name yes / no number TAKEN TYPE sPARE PARTs KIT Component Description Q-ty Fuse 0.315A, 5x20 Key, 10mm Screw, 2.9x13 mm, DIN7981 Screw with interrupted thread, M3x16...
  • Page 20 Address: 14A Srebarna Str., 1407 Sofia, Bulgaria Tel: (+359 2) 9694 800, Fax: (+359 2) 962 52 13 e-mail: info@teletek-electronics.bg www.teletek-electronics.com...

This manual is also suitable for:

Mag8

Table of Contents