General Information; Technical Specifications; General Technical Specifications Of Mag8Plus - Teletek electronics MAG8Plus Installation And Operation Manual

Fire control panel
Table of Contents

Advertisement

1. GENERAL INFORMATION

The MAG8Plus is a conventional microprocessor fire control panel, designed
according to EN54 Standard requirements. The panel provides for monitoring
and reporting fire events in up to 16 separate zones, depending on the installed
configuration.
The MAG8Plus must be installed according to the Fire Alarm Installation Regulations,
mandatory for the territory of the respective country. The electrical power supply to
the panel must be isolated and must not be capable of being accidentally switched
off. The power switch-off board should display a clear FIRE ALARM - DO NOT
SWITCH OFF label.

2. TEChNICAL SPECIFICATIONS

2.1 General Technical Specifications of MAG8Plus

▪ Maximum number of detectors per zone: - Up to 32 conventional detectors with
▪ Thresholds for zone conditions:
• 0 ÷ 2 mA
• 2 ÷ 10 mA
• 10 ÷110 mA
• > 110 mA
▪ Power Supply:
• Main Power Supply
• Stand-by Power Supply
▪ Consumption from 230v in normal
working mode and a fully charged
battery:
• At 4 zones (1 Zone Expander)
• At 16 zones (4 Zone Expanders)
▪ Consumption from the battery at mains
power supply failure in normal working
mode:
• With connected 1 Zone Expander
• With connected 4 Zone Expanders
▪ Consumption from the battery in Fire alarm
condition:
• At 1 Zone Expander, Fire in 1 zone
• At 1 Zone Expander, Fire in 4 zones
▪ Outputs:
• Sounder circuits SND1÷SND4
(control module)
4
MAG8Plus - Installation and Operation Manual
consumption < 200µА at a normal mode;
- Unlimited number of manual call points.
- Open circuit fault condition.
- Normal condition.
- Fire alarm condition.
- Short circuit condition.
~ 230V AC ±10%
2А Fuse, T -Type.
1 Accumulator battery 12V/ 18Ah
Dimensions - 167х181х76mm
Voltage Output - U
Current Output - I
MAX
7А Fuse, Resettable (PTC)
Battery connection: with a flat terminal
lug Ø5mm
2,1VA
4,2VA
130mA
260mA
330mA
720mA
+24V/ 0.3A
Resettable (PTC) Fuse
= 13,8V
CHARGE
= 2A

Advertisement

Table of Contents