This manual contains an information about the limitations in using and operation of the product, as and information about the limits in the responsibility of the manufacturer. Please read the operation manual carefully before starting the installation. MAG8Plus - Installation and Operation Manual...
16 separate zones, depending on the installed configuration. The MAG8Plus must be installed according to the Fire Alarm Installation Regulations, mandatory for the territory of the respective country. The electrical power supply to the panel must be isolated and must not be capable of being accidentally switched off.
• Humidity Up to 93% (non condensing) WARNINGS: Prior to connecting the MAG8Plus Fire Alarm Panel, perform a thorough test of the all wiring integrity of the entire system. Should a fault arise during installation and connection, which cannot be removed, stop the installation and call the producer or his regional...
230 V clamps, to the metal bottom clamps and to the chassis. • After all system programming and testing operation are complete, screw both secure bolts with the help of the hexagonal tool supplied. Figure 1. Figure 2. Figure 3. MAG8Plus - Installation and Operation Manual...
• 2 - Clamp for supporting the main power supply cable. • 3 - Terminal for connecting between the mains power supply and the power source. T-type fuse 2A (Position 3, page 31). • 4 - Earthing point. MAG8Plus - Installation and Operation Manual...
- Jumper for enable/disable Earth Fault Indication; - Resettable (PTC) fuses; - Connector for connecting the main power source; - Connector for connecting 4-zone / 4-sounder expander; - Connector for connecting the control panel keypad. MAG8Plus - Installation and Operation Manual...
Attention: It is possible that the battery might not be charged at the panel initial start-up. In this case the BATT LOW/LOST at the control module and the GENERAL FAULT at the front panel will light on until the battery will be charged up to the required level. MAG8Plus - Installation and Operation Manual...
Before connecting or disconnecting the expander you SHOULD check whether the main and the stand-by power supplies are OFF! The metal box of MAG8Plus can accommodate up to 4-zone expanders. To each zone can be connected up to 32 conventional detectors with consumption <200µA at normal operation mode and unlimited number of manual call points.
5 6 7 8 First First Second а) Control First First Second Control 4 Sounder 4 Zone 4 Zone panel 4 Zone 4 Sounder 4 Zones panel Expander Expander Expander Expander Expander Expander Figure 16. MAG8Plus - Installation and Operation Manual...
4. CONNECTING 4.1 Relay Module MR8 MR8 is a supplementary module which is located outside the MAG8Plus Alarm Panel box. The MR8 contains 8 changeover contact relays. When using all 16 zones, the MAG8Plus needs two relay modules. The technical specifications of the MR8 module relays are described in item 2.2.
Page 14
Figure 17. Terminals and jumper configuration of MR8. Figure 18. Master Connecting between Panel one Relay Module MAG8Plus and Master Panel. Master Figure19. Panel Connecting between MAG8Plus two Relay Modules and Master Panel. MAG8Plus - Installation and Operation Manual...
4.2 Repeater Panel A second MAG8Plus can be connected to the MAG8Plus Fire Alarm panel as Slave. The function of the Slave is to double the light and sound indication and the button control of the first panel at a distance up to 1000 m. For the purpose, to both of the panels have to be assigned specific priorities: The first fire alarm panel shall be the system Master and the second - Slave.
Up to 32 conventional fire detectors and an unlimited number of manual call points can be connected to each circuit. Figure 23 shows how to connect detectors within a zone. Figure 23. Connecting of detectors (D1÷N) and manual call points (CP1÷N) to the zone circuit. MAG8Plus - Installation and Operation Manual...
Page 17
Figure 24 shows how to connect the sounders. One R=10K resistor is connected to the end of each circuit as shown in the diagram. LEGEND black brown Figure 24. Connecting of sounders to SND1÷SND4 outputs of the control module and the output of the 4-sounder expander. MAG8Plus - Installation and Operation Manual...
In case of call point activation, the programmed sounder time delay will be ignored and the sounders will be activated immediately. In order to program MAG8Plus for Sounder Delay over an interval between 1 and 10 minutes: •...
The purpose of introducing a DOUBLE Action mode is to avoid false alarms. Where MAG8Plus has been programmed to function in this mode, in the case of a fire signal, the panel does not alarm at once but waits for the alarm event to be repeated within a specific time interval - Figure 25.
Figure 26. Example for Instant Action Mode Programming. 5.4 Master Panel Mode When connecting two MAG8Plus panels in a common system, the first must be pro- grammed as Master and the second as Slave. In order to program the Master Panel mode: •...
ON position (Access Level 2) all buttons are active. - Operation modes LED indication. - LED indication on zone status. - Control buttons. - Instructions for working with the fire panel. MAG8Plus - Installation and Operation Manual...
Lights up in red at Fire in the zone. Lights up in yellow at disabled zone. Blinks in yellow: - 1 blink per second at trouble in the zone; - 2 blinks per second at “One Man” Test and disabling of zones. MAG8Plus - Installation and Operation Manual...
LED indication remains. 6.6 Service Modes Zone Enable / Disable Each zone of MAG8Plus can be enabled or disabled. To disable a zone: • Press button: DISABLE/ ENABLE LED blinks.
Page 24
(item 6.1). At this point the sounders are enabled. You can exit the sounder enabling mode also by pressing the button, as in that case the procedure for initial start-up will not run. MAG8Plus - Installation and Operation Manual...
Page 25
Man” Test mode is automatic after the end of the test procedure in the last zone, or at any time by pressing button. A sound signalization is activated at every Service Mode entering . The signalization is deactivated by pressing button. MAG8Plus - Installation and Operation Manual...
NORMAL MODE. NOTE: The fault indication does not show immediately. There is a delay in reporting depending on the type of the fault. After all faults are corrected the panel automatically returns to NORMAL MODE. MAG8Plus - Installation and Operation Manual...
DISABLE • The respective zone LEDs light up in Disabled yellow to indicate disabled zones. zones and/or • The yellow SOUNDER FAULT/DISA- sounders. BLE LED lights up to indicate disabled sounders. MAG8Plus - Installation and Operation Manual...
QUANTITy PER ZONE № LOCATION TOTAL: Ion - Ionisation sensor Ph - Photoelectric sensor RoR - Rate of Rise sensor F/T - Fixed Temperature sensor CP - Call Point System installed by: ..................Telephone/Fax: ..................MAG8Plus - Installation and Operation Manual...