6. DESCRIPTION OF THE OPERATION MODES

In this section you can find detailed descriptions of all operation modes of the Repeater panel. The modes
for reviewing of system events are accessible only from level 1 without entering access code. If no alarm,
fault or warning messages, active tests and disablements are present, then the panel is in normal operation
mode and only the current day and time is displayed. In case of alarm, fault or warning situation is occurred
the panel will display information and text messages for the events.

6.1. Review of Alarm Events

The messages for alarm events are displayed with the highest priority in the system. In case of alarm in the
system the panel will show a list with active alarms at the moment, and ALARMS mode is blinking together
with the number of the first alarm message. Over the button (1) is displayed the total number of the active
alarms. The LED 'General Fire' lights on together with the number of the zone in alarm. The panel is
signaling with continuous sound signal, which can be stopped with pressing the 'Silence buzzer' button. The
activated sounders could be stopped after entering access level 2 or 3 and pressing the 'Silence sounders'
button.
Example:
The User can review also some additional information for every of the alarm events. For this, select the
number of the alarm message using up/ down arrow buttons (the number of the selected event is blinking)
and press ENTER button.
On the screen is displayed information for the loop number and the address of the device sensed the alarm
event. At the bottom of the screen is displayed the day and time of occurring of the respective event. Note
that the additional information is different according the type of the alarm event. To exit the review alarm
events mode, press CANCEL button.

6.2. Review of Fault Events

The messages for fault events are displayed with high priority. If no alarm events are present, and there are
active faults in the system, the FAULTS mode is blinking together with the number of the first fault event.
The LED 'General Fault' lights on. The faults messages are cleared automatically after the fault condition is
restored.
Example:
The User can review also some additional information for every of the faults events. For this, select the
number of the fault message using up/ down arrow buttons (the number of the selected event is blinking) and
press ENTER button. In case, there are active alarms in the system, but you want to review the fault
messages, press button (2) – FAULTS mode. The present faults in the system are displayed with serial
numbers. The reviewing is the same as described in item 6.1. The total number of active faults is displayed at
the bottom right corner of the screen. Use button (1) to go back to ALARMS mode and reviewing the alarm
messages.
To review the FAULTS at active alarms in the system:
To exit the review fault events mode, press CANCEL button.