Other Pump Control Algorithms
Set Relays to ALTERNATE DUTY BACKUP [MR 200]
Parameter
P111
P111
P111
Set the Relay ON Setpoints [MR 200]
Parameter
P112
P112
P112
Set the Relay OFF Setpoints [MR 200]
Parameter
P113
Set Relays to FIXED DUTY ASSIST
Parameter
P111
P111
P111
Set the Relay ON Setpoints
Parameter
P112
P112
P112
Set the Relay OFF Setpoints
Parameter
P113
Page 60
MultiRanger 100/200 – INSTRUCTION MANUAL
Index
Value Description
1
53
Sets the pump relays (index 1, 2, and 3) to
2
53
ALTERNATE DUTY BACKUP .
3
53
Index
Value Description
1
0.4m
Sets the three setpoints for the pump relays.
The first cycle will use these setpoints.
2
0.3m
Subsequent cycles rotate the setpoints
3
0.2m
among the pumps.
Index
Value Description
0
1.3m
By using index 0 all six relays are set at the
same time, including any alarm relays. Use
with caution.
Index
Value Description
1
50
Sets the pump relays (index 1, 2, and 3) to
FIXED DUTY ASSIST. Multiple pumps can run
2
50
simultaneously.
3
50
Index
Value Description
1
0.4m
Sets the three setpoints for the pump relays.
The first cycle will use these setpoints.
2
0.3m
Subsequent cycles rotate the setpoints
3
0.2m
among the pumps.
Index
Value Description
0
1.3m
By using index 0 all six relays are set at the
same time, including any alarm relays. Use
with caution.
7ML19981FB05