Backup Level Override; Backup Level Override Parameters - Siemens MAG 1100 Operating Instructions Manual

Electromagnetic flowmeters
Table of Contents

Advertisement

Backup Level Override

Backup level override provides the option of overriding the ultrasonic input with another
contacting point level device, for example, the Pointek CLS 200. The ultrasonic reading is
fixed at the programmed switch level until the discrete input is released and the
ultrasonic device makes its decisions based on the override value.

Backup Level Override Parameters

P064: Reading Override Enable
Sets the discrete input as the source of a level reading override.
P065: Reading Override Value
Substitutes value for current reading when the discrete input (P064) is enabled. Value is
added in current units and is valid only for the following:
level
space
distance
difference
average modes of operation
head level in OCM mode
Example:
A high level backup switch is connected to Digital Input Two in the same application as
Transducer One at level value 4.3 m.
Settings
Parameter
P064
P064
P065
P065
When the level rises to 4.3 m and the switch is activated, the reading is forced to 4.3 m
where it stays until the switch is de-activated.
P066: Override Time Delay
Sets the time (in seconds) used to calm the override condition input.
Page 46
MultiRanger 100/200 – INSTRUCTION MANUAL
Index
Value
1
2
2
0
1
4.3
2
7ML19981FB05

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mag 1100 fMag 3100Mag 3100 pMag 5100 wMag 5000Mag 6000

Table of Contents