Siemens MAG 1100 Operating Instructions Manual page 233

Electromagnetic flowmeters
Table of Contents

Advertisement

Set the Common Parameters
Prerequisite: Substitute the details of your application in place of the sample values
provided. If you are bench testing the unit, set your test values to be the same as the
sample values.
Parameter
P001
P002
P003
P004
P005
P006
P007
1.
Example assumes a single measurement unit. If your MultiRanger has
dual point software installed, some parameters are indexed by two.
Set Relays to ALTERNATE DUTY ASSIST
Parameter
P111
P111
P111
Set the Relay ON Setpoints
Parameter
P112
P112
P112
Set the Relay OFF Setpoints
Parameter
P113
For more information, see
7ML19981FB05
MultiRanger 100/200 – INSTRUCTION MANUAL
1
Value Description
Index
G
1
Operation = level
G
1
Material = liquid
G
2
Maximum Process Speed = medium
G
102
Transducer = XPS-10
G
1
Units = meters
G
1.8
Empty = 1.8m
G
1.4
Span = 1.4m
Index
Value Description
1
52
Sets the pump relays (index 1, 2, and 3) to
2
52
ALTERNATE DUTY ASSIST.
3
52
Index
Value Description
1
0.4m
Sets the three setpoints for the pump relays.
The first cycle will use these setpoints.
2
0.3m
Subsequent cycles rotate the setpoints
3
0.2m
among the pumps.
Index
Value Description
0
1.3m
Appendix D: Pump Control Reference
By using index 0 all six relays are set at the
same time, including any alarm relays. Use
with caution.
on page 239.
Page 59

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mag 1100 fMag 3100Mag 3100 pMag 5100 wMag 5000Mag 6000

Table of Contents