Siemens MAG 1100 Operating Instructions Manual page 316

Electromagnetic flowmeters
Table of Contents

Advertisement

P131 Pump Run-On Duration [MR 200]
Sets the number of seconds that the pump runs on.
Primary Index
Values
Related
Your pump capacity determines the amount of material that can be removed. Choose a
value long enough to clean out the vessel bottom, yet short enough not to run the pump
dry. Also be sure that this value does not overlap with P130 (Interval). The timing should
look something like this:
P131
P132 Pump Start Delay [MR 200]
Sets the minimum delay (in seconds) between pump starts.
Primary Index
Values
Related
Use this feature to reduce a power surge from all pumps starting at the same time. This
delay determines when the next pump is permitted to start.
P133 Pump Power Resumption Delay [MR 200]
Sets the minimum delay before the first pump restarts after power failure.
Primary Index
Values
Related
This reduces the surge from the first pump starting immediately on power resumption.
When this delay expires, other pumps will start as per P132.
Page 142
MultiRanger 100/200 – INSTRUCTION MANUAL
Global
Range: 0.0 to 9999
Preset: 0.000
Advanced Pump Control Modifiers (P130 to P136)
P130 (Pump Run-On)
Global
Range: 0.0 to 9999
Preset: 10 seconds
Value is divided by 10 in simulation mode.
Advanced Pump Control Modifiers (P130 to P136)
P121 Pump by Rate
Global
Range: 0.000 to 9999
Preset: 10 seconds
Advanced Pump Control Modifiers (P130 to P136)
P132 Pump Start Delay
P132
7ML19981FB05