P820 Algorithm
Chooses the algorithm to generate the measured value from the profile.
Primary Index
Values
Related
Use this to select the algorithm(s) the Sonic Intelligence® echo selection is based on.
Use P805 Echo Confidence (page 202) to determine which algorithm gives the highest
confidence under all level conditions. If the wrong echo is processed, observe the echo
processing displays and select an alternate algorithm, either by entering the numeric
value desired, or as below:
1.
Press MEASURE
2.
Press ARROWS
3.
Press ENTER
Page 204
MultiRanger 100/200 – INSTRUCTION MANUAL
Single Point Model
Global
1
ALF = flat Area, Largest, and First average
2
A = flat Area only
3
L = flat Largest only
4
F = flat First only
5
AL = flat Area and Largest average
6
AF = flat Area and First average
7
LF = flat Largest and First average
8
*
bLF = smooth Largest or First
9
bL = smooth Largest only
10
bF = smooth First only
12
tF = true First only
P805 Echo Confidence
P821 Spike Filter
P822 Narrow Echo Filter
P823 Reform Echo
P825 Echo Marker Trigger
to display the Auxiliary Function symbol.
to access the desired Reading display symbols.
when the required algorithm is displayed.
Dual Point Model
Transducer
7ML19981FB05