mA I/O

To integrate the MultiRanger with other equipment, use the mA input and outputs.
When a mA input parameter is accessed, a mA symbol appears in the
Note:
upper left corner of the LCD display.
The mA input can be used as a level measurement or can be passed on to a SCADA
system.

mA Input [MR 200]

Level Reading Parameters
Parameter
P004
P250
P251
P252
P253
To pass the mA input on to a SCADA system, read the value from the appropriate
communication registers. For more information, go to the
section on page 89.

mA Output

The MultiRanger has two mA outputs, used to send measurements to other devices.
Configuring the mA output to send a 4 to 20 mA signal scaled from 10% to 90% of span of
the second transducer:
Parameter
P200
P201
P202
P210
P211
P219
1.
If the level reading drops below 10% of span, the mA output drops below
4 mA.
2.
If the level reading rises above 90% of span, the mA output rises above
20 mA.
Page 48
MultiRanger 100/200 – INSTRUCTION MANUAL
Index
Value
Description
1
250
Transducer = mA input 1
1
2
Scale = 4 to 20 mA
1
0
4 mA = 0% of span
1
100
20 mA = 100% of span
1
0
Do not damp the input signal
Index
Value Description
1
2
set to 4 to 20 range
1
1
send mA proportional to level reading
1
2
base mA on level point 2
1
10
set 4 mA at 10% of span
1
90
set 20 mA at 90% of span
1
0
set failsafe action as 0 mA
MultiRanger Communications
1
2
7ML19981FB05