P136 Wall Cling Reduction [MR 200]
Varies the upper and lower setpoints to reduce material buildup on the walls.
Primary Index
Values
This value is the range in which the setpoints are allowed to deviate in percent or units.
The Relay Setpoints ON and OFF values are randomly varied inside the range to ensure
that the material level does not consistently stop at the same point.
Random Setpoint Range
P137 Pump Group [MR 200]
Puts pumps into groups for multiple pump rotations on one transducer.
Primary Index
Values
Alters
This feature groups pumps (relay points 1 - 6) into groups 1 or 2. It is applied to pump
rotation and occurs independently within each group.
7ML19981FB05
MultiRanger 100/200 – INSTRUCTION MANUAL
Single Point Model
Global
Range: 0.000 to 9999
Preset: 0.000
Relay
Range: 1 to 2
1
*
group 1
2
group 2
P111 Relay Control Function when P111=52 (Alternate duty
assist) or 53 (Alternate duty backup)
Dual Point Model
Transducer
Level Setpoint ON
Wall Cling Value
Level Setpoint OFF