Setting Simple Level Alarms

To set Relay Five to a standard level alarm (Hi Hi, Hi, Lo, Lo Lo) do the following:
Parameter Index Value Description
P111
P112
P113
Available designations:
Alarm
Hi Hi
Hi
Lo
Lo Lo

Rate [MR 200]

Rate alarms can trigger an alarm if the vessel is filling/emptying too quickly.
Setting a Filling Rate Alarm
Parameter
P111
P112
P113
Setting an Emptying Rate Alarm
Parameter
P111
P112
P113
Page 54
MultiRanger 100/200 – INSTRUCTION MANUAL
5
1
Set P111, indexed to relay, to the value 1 for level
alarm
Press UNIT
symbol.
Press ARROW keys
to the alarm designation ( , , , or ).
Press ENTER
5
1.2m
Set the ON setpoint
5
1.15m •
Set the OFF setpoint
Designation
Index
Value Description
5
4
These settings trip the alarm when the
reservoir is filling faster than 1m per minute
5
1m
and reset it at 0.9m per minute.
5
0.9m
Index
Value Description
5
4
These settings trip the alarm when the
reservoir is emptying faster than 10% of span
5
-10%
per minute and reset the alarm when
5
-5%
emptying falls to 5%.
to display the Auxiliary Function
as required to scroll
to enter the value.