Configuring BACnet Device Instance and network number

The TV-PSM controller must have a unique Device Instance and Name. These BACnet addresses are automatically
generated and usually do not require modification. However, sometimes you need to override the automatic
addressing assignments.
Autogenerated addressing scheme:
The TV-PSM's rotary address setting determines the automatic BACnet addressing scheme for the connected
Open network.
Legend
16 = Carrier's BACnet Vendor ID
xxx = TV-PSM's rotary switch address (See NOTES below.)
yy = Controller's rotary switch address (ARCNET/MSTP MAC address)
For the TV-PSM:
BACnet Device Instance Number = (IP network number x 100) + rotary switch address
BACnet Device Instance Name = the name "device" + the Device Instance
BACnet IP Network Number = 1600
BACnet ARC/MSTP Port S1 Network Number = ((IP network number + rotary switch address) x 10)
Port S1 MSTP MAC Address = 0 by default (user configurable)
Port S1 ARCNET Address = 254 by default (user configurable)
BACnet MSTP Port S2 Network Number = ((IP network number + rotary switch address) x 10) +3
Port S2 MSTP MAC Address = 0 by default (user configurable)
For the Open controllers connected to the TV-PSM
BACnet MSTP Device Instance Number = BACnet MSTP Network Number + yy
BACnet ARCNET Device Instance Number = BACnet ARCNET Network Number +yy
BACnet MSTP Device Instance Name = the name "device" + Device Instance
BACnet ARCNET Device Instance Name = the name "device" + Device Instance
BACnet MSTP or ARCNET MAC Address = yy
BACnet MSTP Network Number = 161xx (learned from the router, defaults to 16101 if no TV-PSM is
operating)
NOTES
Do not configure the rotary switches on the TV-PSM to a number greater than 127 unless Port S1 is enabled
for ARCNET. Doing so will not allow the i-Vu® server to discover the TV-PSM.
If you change the TV-PSM's switches or jumpers, you must cycle its power for the changes to take effect.
If the BACnet automatic settings need to be changed, see To communicate through the Local Access port
(page 42).
TruVu™ ChillerVu™ Plant Controller
Installation and Start-up Guide
21
Addressing the TV-PSM