Configuring BACnet Device Instance and network number
The TV-PSM controller must have a unique Device Instance and Name. These BACnet addresses are automatically
generated and usually do not require modification. However, sometimes you need to override the automatic
addressing assignments.
Autogenerated addressing scheme:
The TV-PSM's rotary address setting determines the automatic BACnet addressing scheme for the connected
Open network.
Legend
16 = Carrier's BACnet Vendor ID
xxx = TV-PSM's rotary switch address (See NOTES below.)
yy = Controller's rotary switch address (ARCNET/MSTP MAC address)
For the TV-PSM:
•
BACnet Device Instance Number = (IP network number x 100) + rotary switch address
•
BACnet Device Instance Name = the name "device" + the Device Instance
•
BACnet IP Network Number = 1600
•
BACnet ARC/MSTP Port S1 Network Number = ((IP network number + rotary switch address) x 10)
•
Port S1 MSTP MAC Address = 0 by default (user configurable)
•
Port S1 ARCNET Address = 254 by default (user configurable)
•
BACnet MSTP Port S2 Network Number = ((IP network number + rotary switch address) x 10) +3
•
Port S2 MSTP MAC Address = 0 by default (user configurable)
For the Open controllers connected to the TV-PSM
•
BACnet MSTP Device Instance Number = BACnet MSTP Network Number + yy
•
BACnet ARCNET Device Instance Number = BACnet ARCNET Network Number +yy
•
BACnet MSTP Device Instance Name = the name "device" + Device Instance
•
BACnet ARCNET Device Instance Name = the name "device" + Device Instance
•
BACnet MSTP or ARCNET MAC Address = yy
•
BACnet MSTP Network Number = 161xx (learned from the router, defaults to 16101 if no TV-PSM is
operating)
NOTES
•
Do not configure the rotary switches on the TV-PSM to a number greater than 127 unless Port S1 is enabled
for ARCNET. Doing so will not allow the i-Vu® server to discover the TV-PSM.
If you change the TV-PSM's switches or jumpers, you must cycle its power for the changes to take effect.
•
If the BACnet automatic settings need to be changed, see To communicate through the Local Access port
(page 42).
TruVu™ ChillerVu™ Plant Controller
Installation and Start-up Guide
21