Table 36: Signal Type "Namur Ne43", Amount/Sign Format - WAGO 750 XTR Manual

4ai u/i diff galv xtr 4-channel analog input; for voltage/current; extreme
Hide thumbs Also See for 750 XTR:
Table of Contents

Advertisement

WAGO I/O System 750 XTR
750-471/040-000 4AI U/I Diff Galv XTR

Table 36: Signal Type "Namur NE43", Amount/sign format

Measuring range [mA]
Namur NE43
< −14,0 mA
Neg. sensor overload
< 1,0
Wire break or
Overload
< 3,6
Underrange
3,8
4,0
5,6
7,2
8,8
10,4
12,0
13,6
15,2
16,8
18,4
20,0
20,5
Exceeding
> 21,0
Sensor overload
> 22,0
1)
When underrange / overrange limit is ON
2)
When wire break / overload diagnostics is ON
Binary
1000.0001.1000.1100
3)
1000.0001.1000.1100
2)
1000.0001.1000.1100
1)
1000.0001.1000.1100
0000.0000.0000.0000
0000.1100.0110.1001
0001.1000.1100.1010
0010.0101.0011.1100
0011.0001.1010.0110
0011.1110.0000.1111
0100.1010.0111.1000
0101.0110.1110.0010
0110.0011.0100.1011
0110.1111.1011.0100
0111.1100.0001.1110
0111.1111.1111.1111
1)
0111.1111.1111.1111
2)
0111.1111.1111.1111
Process value
Hex.
Dec.
0x818C
−397
0x818C
−397
0x818C
−397
0x818C
−397
0x0000
0x0C69
3177
0x18CA
6346
0x253C
9532
0x31A6
12710
0x3E0F
15887
0x4A78
19064
0x56E2
22242
0x634B
25419
0x6FB4
28596
0x7C1E
31774
0x7FFF
32767
0x7FFF
32767
0x7FFF
32767
Process Image
51
Statusbyte
Error
hex.
LED
0x50
on
0x60
on
0x41
on
0x00
off
0
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x42
on
0x50
on
Manual
Version 1.0.2

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-471/040-000

Table of Contents