Table 35: Signal Type "Namur Ne43", Two's Complement With Status - WAGO 750 XTR Manual

4ai u/i diff galv xtr 4-channel analog input; for voltage/current; extreme
Hide thumbs Also See for 750 XTR:
Table of Contents

Advertisement

50
Process Image
Table 35: Signal Type "Namur NE43", Two's Complement with Status Information in the Process
Image
Measuring range [mA]
Namur NE43
< −14.0 mA
Neg. sensor overload
< 1.0
Wire break
< 3.6
Underrange
3.8
4.0
5.6
7.2
8.8
10.4
12.0
13.6
15.2
16.8
18.4
20.0
20.5
Exceeding
> 21.0
Sensor overload
> 22.0
1)
Status bits: X: not used, F= error, Ü= overrange
2)
When underrange / overrange limit is ON
3)
When wire break / overload diagnostics is ON
Manual
Version 1.0.2
Binary
1111.1110.0111.0
3)
1111.1110.0111.0
3)
1111.1110.0111.0
2)
1111.1110.0111.0
0000.0000.0000.0
0000.1100.0110.1
0001.1000.1100.1
0010.0101.0011.1
0011.0001.1010.0
0011.1110.0000.1
0100.1010.0111.1
0101.0110.1110.0
0110.0011.0100.1
0110.1111.1011.0
0111.1100.0001.1
0111.1111.1111.1
2)
0111.1111.1111.1
3)
0111.1111.1111.1
WAGO I/O System 750 XTR
750-471/040-000 4AI U/I Diff Galv XTR
Process value
Hex.
XFÜ
1)
011
0xFE73
011
0xFE73
011
0xFE73
000
0xFE70
000
0x0000
000
0x0C68
000
0x18C8
000
0x2538
000
0x31A0 12704
000
0x3E08 15880
000
0x4A78 19064
000
0x56E0 22240
000
0x6348 25416
000
0x6FB0 28592
000
0x7C18 31768
000
0x7FF8 32760
011
0x7FFB 32763
011
0x7FFB 32763
Status
Error
byte hex.
LED
Dec.
−397
0x50
on
−397
0x60
on
−397
0x41
on
−400
0x00
off
0
0x00
off
3176
0x00
off
6344
0x00
off
9528
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x42
on
0x50
on