Table 14: Technical Data – Power Jumper Contacts
Power jumper contacts
Table 15: Technical Data – Data Contacts
Data contacts
3.5.7

Mechanical Conditions

Table 16: Technical Data – Mechanical Conditions
Vibration resistance
*
Follow the installation instructions
3.5.8

Climatic Environmental Conditions

Table 17: Technical Data ‒ Climatic Environmental Conditions
Surrounding air temperature, operation
Surrounding air temperature, storage
Relative humidity
Elevation above sea level
Resistance to harmful substances
Maximum pollutant concentration at
relative humidity < 75 %
Special conditions
*)
Short-term condensation acc. class 3K7 / IEC EN 60721-3-3 permitted, applying
E-DIN 40046-721-3 (except wind-driven precipitation, water and ice formation)
Manual
Version 1.0.2
*)
without temperature derating
with temperature derating
WAGO I/O System 750 XTR
750-471/040-000 4AI U/I Diff Galv XTR
Blade/spring contact, self-cleaning, hard
gold plated
Slide contact, self-cleaning, hard gold
plated
Max. 5g
*
−40 °C ... +70 °C
−40 °C ... +85 °C
95 %
0 m ... 2000 m
2000 m ... 5000 m:
max.
5000 m
Acc. to IEC 60068-2-42 and
IEC 60068-2-43
SO
≤ 25 ppm
2
H
S ≤ 10 ppm
2
The permissible temperature range of
the connecting cable must be
dimensioned based on the mounting
position and current intensity, as the
temperature of the terminal connection
can be up to 25 K above the maximum
expected surrounding air temperature
(at 10 A).
0.5 K per 100 m