Table 33: Signal Types "±10 V", "±200 Mv" "±20 Ma", Amount/Sign Format - WAGO 750 XTR Manual

4ai u/i diff galv xtr 4-channel analog input; for voltage/current; extreme
Hide thumbs Also See for 750 XTR:
Table of Contents

Advertisement

48
Process Image
Table 33: Signal Types "±10 V", "±200 mV" "±20 mA", Amount/sign format with Status Information in
the Process Image
Measuring range
± 10 V
± 200 mV
n.a.
Neg. sensor overload
< −10.4
< −210.0
Underrange
−10.0
−6.0
−2.0
0.0
2.0
6.0
10.0
Exceeding
> 10.4
Sensor overload
n.a.
1)
Status bits: X: not used, F= error, Ü= overrange
2)
When underrange / overrange limit is ON
3)
When wire break / overload diagnostics is ON
Manual
Version 1.0.2
± 20 mA
Measuring value XFÜ
n.a.
< −22.0
1111.1111.1111.1
3)
< −21.0
1111.1111.1111.1
2)
−200.0
−20.0
1111.1111.1111.1
−120.0
−12.0
1100.1100.1100.1
−40.0
−4.0
1001.1001.1001.1
0.0
0.0
0000.0000.0000.0
40.0
4.0
0001.1001.1001.1
120.0
12.0
0100.1100.1100.1
200.0
20.0
0111.1111.1111.1
2)
0111.1111.1111.1
> 210.0
> 21.0
3)
0111.1111.1111.1
n.a.
> 22.0
WAGO I/O System 750 XTR
750-471/040-000 4AI U/I Diff Galv XTR
Process value
Binary
Hex.
1)
011
0xFFFB
011
0xFFFB
000
0xFFF8
000
0xCCC8
000
0x9998
000
0x0000
000
0x1998
000
0x4CC8
000
0x7FF8
011
0x7FFB
011
0x7FFB
Status
Error
byte
LED
Dec.
hex.
−32763
0x50
on
−32763
0x41
on
−32760
0x00
off
−19656
0x00
off
−6552
0x00
off
0
0x00
off
6552
0x00
off
19656
0x00
off
32760
0x00
off
32763
0x42
on
32763
0x50
on

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-471/040-000

Table of Contents