Scaling - WAGO 750 XTR Manual

4ai u/i diff galv xtr 4-channel analog input; for voltage/current; extreme
Hide thumbs Also See for 750 XTR:
Table of Contents

Advertisement

66
Commissioning
Table 41: Parameter „Channel"
Selection Field
Diagnosis: Measuring
range overflow
Diagnosis: Measuring
range underflow
Diagnosis: Upper user
limit exeeded
Diagnosis: Lower user
limit undershot
Lower user limit
Upper user limit
*)
Factory setting
Save settings!
Click the [Write] button to transmit any settings that have been made to the I/O
module!
7.1.4.3

Scaling

The settings entered in the "Scaling" dialog window directly affect the process
value. Scaling is carried out for each channel and is saved permanently, i.e.
available after restarting the node.
Manual
Version 1.0.2
750-471/040-000 4AI U/I Diff Galv XTR
Possible Settings
Off*
Wire break diagnostics is OFF.
The measurement overrange diagnostics can be
switched on or off here.
Off
Measurement overrange diagnostics is
OFF.
On*
Measurement overrange diagnostics is
ON.
The measurement underrange diagnostics can be
switched on or off here.
Off
Measurement underrange diagnostics is
OFF.
On*
Measurement underrange diagnostics is
ON.
The user limit overrange diagnostics can be switched
on or off here.
Off
User limit overrange diagnostics is OFF.
On*
User limit overrange diagnostics is ON.
The user limit underrange diagnostics can be switched
on or off here.
Off
User limit underrange diagnostics is OFF.
On*
User limit underrange diagnostics is ON.
32767*
The upper user limit value can be entered
in the entry field.
-32768*
The lower user limit value can be entered
in the entry field.