Alarm
Stream Conflict
Temperature Internal
Tie Failure
Video loss
Cause
Multiple NAV endpoints are configured
to use the same video, audio, or AES67
multicast IP address.
The NAV device is overheating.
The encoder failed to establish a tie with
the specified endpoint.
The input is changed and video sync
cannot be established for within a
2-second window.
Remedy
Reconfigure endpoint stream settings for
a unique stream address.
Check the ambient temperature of the
NAV device installation location.
If greater than 104°F, (60ºC) use
HVAC system to lower ambient
temperature.
If ambient temperature is
104°F, (60°C) or less, check the
mounting location for nearby
equipment emitting excessive heat.
Debug the network connectivity between
the encoder and decoder.
Debug the connectivity of the AV source
device to the NAV encoder.
NAV E 101 Encoder • Troubleshooting