REVO C
2PH from 60A to 800A - 690V
Parameter Name
Set the gain for the main loop. A larger
Pb Power
value yields a larger adjustment for a
given deviation
Set how aggressively the integral part
Ti Power
of the control algorithm acts. A larger
settings yields a larger adjustment for
a given deviation over a given time
Set the threshold of resistance that
HB Sense
activates the Heater Break alarm. This
setting is in percentage of the nominal
load resistance
Set a delay between when the
HB Delay
resistance drops below the value set
for a heater break sensitivity and when
the heater break alarm is indicated.
This set increments of 50mSec
Logging
Enable or disable data logging on the
internal SD card
Parameter Name
Log Period
Set how often data is logged
Description
Option
Value
Off
0
On
DEFAULT: Off
0
Description
Default
10%
50
100%
50
(2,5 sec)
0
1
Default
5 sec
45
User's manual
Modbus
Range
Unit
Address
0 to 255
%
26
0 to 255
27
0 to 100.0
%
29
0 to 255
(0 to 12,75
28
sec)
139
Modbus
Range
Unit
Address
0 to 255
sec
70
Par.
Type
Read
Write
Read
Write
Read
Write
Read
Write
Read
Write
Par.
Type
Read
Write
Need help?