USER'S MANUAL
Rev. 05/2022
003
CD Automation S.r.l.
Via Picasso, 34/36 - 20025 Legnano (MI)- Italy
Tel. +39 0331 577479 - Fax +39 0331 579479
E-mail: info@cdautomation.com - Web: www.cdautomation.com
CD3000S
1PH
From 10 to 90A
M-3000S1-10-90

Advertisement

Table of Contents
loading

Summary of Contents for CD Automation CD3000S 1PH

  • Page 1 CD3000S USER’S MANUAL Rev. 05/2022 From 10 to 90A M-3000S1-10-90 CD Automation S.r.l. Via Picasso, 34/36 - 20025 Legnano (MI)- Italy Tel. +39 0331 577479 - Fax +39 0331 579479 E-mail: info@cdautomation.com - Web: www.cdautomation.com...
  • Page 2: Declaration Of Conformity

    P.I. 08925720156 -Tel. +39 0331 577479 - Fax +39 0331 579479 E-mail: info@cdautomation.com - Web: www.cdautomation.com Declare that the product / Dichiara che il prodotto: CD3000S 1PH 10-90A PRODUCT DESCRIPTION: Electric power control SCOPE OF APPLICATION: Thermal control process DESCRIZIONE DEL PRODOTTO: Unità di controllo potenza elettrica...
  • Page 3 P.I. 08925720156 -Tel. +39 0331 577479 - Fax +39 0331 579479 E-mail: info@cdautomation.com - Web: www.cdautomation.com Declare that the product / Dichiara che il prodotto: CD3000S 1PH 10-90A PRODUCT DESCRIPTION: Electric power control SCOPE OF APPLICATION: Thermal control process DESCRIZIONE DEL PRODOTTO: Unità di controllo potenza elettrica...
  • Page 4: Important Warnings For Safety

    User’s manual CD3000S 1PH from 10A to 90A Important warnings for safety This chapter contains important information for the safety. The not observance of these instructions may result in serious personal injury or death and can cause serious damages to the Thyristor unit and to the components system included.
  • Page 5 User’s manual CD3000S 1PH from 10A to 90A WARNING! All service including inspection, installation, wiring, maintenance, troubleshooting, fuse or other user serviceable component replacement must be performed only by properly qualified personnel. Service personnel must read this manual before proceeding with work. While service is being performed unqualified personnel should not work on the unit or be allowed in the immediate vicinity.
  • Page 6 User’s manual CD3000S 1PH from 10A to 90A AVERTISSEMENT! Au moment de relever des mesures de tension ou de courant en direct, utiliser un équipement de protection individuelle approprié pour les tensions et les potentiels d’arc électrique concernés. WARNING! Verify the voltage and current ratings of the power controller are correct for the application. AVERTISSEMENT! Vérifier que les valeurs de tension et de courant du régulateur de puissance sont correctes pour l’application.
  • Page 7: Maintenance

    Substituted parts remain of Producer property. CD Automation srl assumes no liability for any damage to persons or property deriving from tampering, from incorrect or improper use, or from any use not conforming to the characteristics of the controller and to the instructions in this User Manual.
  • Page 8: Table Of Contents

    User’s manual CD3000S 1PH from 10A to 90A Summary Declaration of conformity ........2 Important warnings for safety .
  • Page 9: Quick Start

    User’s manual CD3000S 1PH from 10A to 90A Quick Start 1.1 Standard version Attention: this procedure must be carried out by skilled people only. If the Order Code of the Thyristor unit is in line with what you really need, then CD3000S has been already configured in Factory and you just need to do the following steps: Verify CD3000S Sizing.
  • Page 10: Basic Connections And Sizing

    User’s manual CD3000S 1PH from 10A to 90A Basic Connections and sizing Wiring with resistive Load I= P V V = Nominal voltage of the load I = Nominal current of the load P = Nominal power of the load Identification and Order Code 3.1 Identification of the Unit Caution: Before to install, make sure that the Thyristor unit have not damages.
  • Page 11: Order Code

    HB Option not available with UL approval New Code (example): CD3000S 1PH Old Code (example): Operating Max Load Current Model Voltage Voltage Voltage Input Firing Fuses Approvals Manual Option Option CD3000S 1PH / 90A / 400V 480V 12:24V / 4-20mA / BF008 /...
  • Page 12: Technical Specification

    User’s manual CD3000S 1PH from 10A to 90A Technical Specification 4.1 General features Cover and Socket material: PolymericV2 Heat-sink: Anodized aluminum Delay switch ON time: 0.5 period Max Delay switch OFF time: 0.5 period Max Auxiliary Voltage: 12÷24V dc/ac (max 70mA) 4.2 Input features Analog Input: 4 - 20mA...
  • Page 13: Environmental Installation Conditions

    User’s manual CD3000S 1PH from 10A to 90A 4.4 Environmental installation conditions Ambient temperature 0-40°C (32-104°F) at nominal current. Over 40°C use the derating curve (max 50°C). Storage temperature -25°C to 70°C, -13°F to 158°F Installation place Don’t install at direct sun light, where there are conductive dust, corrosive gas, vibration or water and also in salty environmental.
  • Page 14: Installation

    User’s manual CD3000S 1PH from 10A to 90A Installation Before to install, make sure that the Thyristor unit have not damages. ≥5 cm If the product has a fault, please contact the dealer from which you purchased the product. Verify that the product is the same thing as ordered.
  • Page 15 User’s manual CD3000S 1PH from 10A to 90A Size: S3 with ICT option Ø 4,5 mm 52 mm 120 mm 140 mm Size: S7 Ø 4,5 mm 65 mm 117 mm 159 mm...
  • Page 16: Wiring Instructions

    User’s manual CD3000S 1PH from 10A to 90A Wiring instructions CD3000S unit has isolated heatsink. For safety connect the heatsink to earth using its terminal with earth symbol. CD3000S can be susceptible to airborne interferences from near equipment or from interferences on main supply, so a number of precautions must be taken.
  • Page 17: Diagram Of Control Connection - Standard Version

    User’s manual CD3000S 1PH from 10A to 90A 6.1 Diagram of control connection - Standard Version Size S0 (2x10A) - Standard version Size S0 - Standard version 15A-25A L2/N L2/N LOAD Input: L1 T1 A1- A2+ Input: Input: L2 T2 B1- B2+ LOAD LOAD...
  • Page 18 User’s manual CD3000S 1PH from 10A to 90A Size S3 - Standard version 35A-45A L2/N L2/N Input: LOAD Note: The user installation must be protecting by electromagnetic circuit breaker or by fuse isolator.
  • Page 19 User’s manual CD3000S 1PH from 10A to 90A Size S7 - Standard version 60A-90A L2/N L2/N Input: LOAD Note: The user installation must be protecting by electromagnetic circuit breaker or by fuse isolator.
  • Page 20: Diagram Of Control Connection - Analog Input And/Or Heater Break Options

    User’s manual CD3000S 1PH from 10A to 90A 6.2 Diagram of control connection - Analog Input and/or Heater Break Options Size S3 with Analog Input and/or Heater Break Option - 35A-45A L2/N L2/N H.B. Alarm 1 2 3 4 5 Ext.
  • Page 21 User’s manual CD3000S 1PH from 10A to 90A Size S7 with Analog Input and/or Heater Break Option - 60A-90A L2/N L2/N C1 C2 C3 H.B. Alarm Ext. CAL 12-24Vdc C.T. Input 0-10Vdc 4-20mA LOAD 12-24V AC/DC Note: 1. The user installation must be protecting by electromagnetic circuit breaker or by fuse isolator. 2.
  • Page 22: Heater Break Alarm And Scr Short Circuit

    User’s manual CD3000S 1PH from 10A to 90A Heater break alarm and SCR short circuit Only with HB option The Heater Break circuit to work properly must have at least an input of 25% of the nominal current. H.B. circuit read load current via a current transformer 25-50/0.05 or 100/0.05 depending on thyristor size. Minimum current is 30% of the current transformer size’s.
  • Page 23: Heater Break Calibration Procedure (Only With The Hb Option)

    User’s manual CD3000S 1PH from 10A to 90A 7.2 Heater break Calibration procedure (only with the HB option) An automatic function sets the Heater Break Alarm. The auto setting function can be activated using the “CAL” button on front unit, or supply with 12-24Vdc the digital input “Cal Ext.
  • Page 24: Firing Setting

    User’s manual CD3000S 1PH from 10A to 90A Firing Setting 8.1 Firing Setting with Analog Input Option The BF firing performed in Digital mode in the Thyristor unit give a lot of advantages because switches Thyristor at zero voltage crossing (ZC) without EMC interferences. Analog input is necessary for BF and can be decided how many complete Cycle we want at 50% of power demand.
  • Page 25: Firing Setting With Heater Break Option

    User’s manual CD3000S 1PH from 10A to 90A 8.2 Firing Setting with Heater Break Option ZC firing mode is used with Logic Output from temperature controllers and the Thyristor operates like a contactor. The Cycle time is performed by temperature controller. ZC minimizes interferences because the Thyristor unit switches ON-OFF at zero voltage.
  • Page 26: Input Setting

    User’s manual CD3000S 1PH from 10A to 90A Input Setting 9.1 Input Setting with Analog Input Option The input type is already configured in line with customer requirements that are defined in the complete product code. However, if you wish to change the input type (ex. from 0÷10V to 4÷20mA) set the jumpers as below represented and then do the “Input calibration procedure”.
  • Page 27: Input Calibration Procedure (Only With Analog Input Option)

    User’s manual CD3000S 1PH from 10A to 90A 9.2 Input Calibration procedure (only with Analog Input Option) Warning: this procedure can be done just by specialized personnel and is needed only if you change the input type. Start TUNE Auxiliary power supply Mantain Key CAL pushed and give the power supply 2sec.
  • Page 28: Fuses And Fuse Holder

    User’s manual CD3000S 1PH from 10A to 90A Fuses and Fuse holder Warning: High speed fuses are only used for the thyristor protection and can not be used to protect the installation. CD3000S unit must be protected against short circuit by High speed fuses. The Fuses must have I²t 20% less than thyristor’s I²t.
  • Page 29 User’s manual CD3000S 1PH from 10A to 90A Fuse Holder size 10-25A 35-45A 42,5 17,8 60-90A 90A UL 75 35 25.5...
  • Page 30 CD Automation S.r.l. Via Picasso, 34/36 - 20025 Legnano (MI) - Italy Tel. +39 0331 577479 - Fax +39 0331 579479 E-mail: info@cdautomation.com - Web: www.cdautomation.com...