2240 YRM 0001
TO LOCATE PROBLEM CELL OR CELLS,
POS./NEG. SIDE, CHECK FOR VOLTAGE
FROM POS/NEG TERMINALS TO
BATTERY FRAME USING THE VOLT-OHM
METER. DIVIDING THAT VOLTAGE BY 2
WILL HELP INDICATE WHAT CELL IS
SHORTED.
Table 2. BATTERY TROUBLESHOOTING GUIDE (Continued)
|
1
|
←————— ——————
|
|
|
|
4
BATTERY LOAD TEST
|
MORE THAN 100MA
————
POSSIBLE SHORTED
|
CONDITION. WASHING OF
|
BATTERY MAY BE
|
REQUIRED
|
INCORRECT
CORRECTED
|
BATTERY SHORTED
CONDITION
|
|
———
REPLACE BATTERY AND
|
CONTACT BATTERY
|
VENDOR
|
|
|
|
|
|
|
|
|
|
|
|
|
←———————————
|
PLACE AMP SHUNT METER IN SERIES
WITH EITHER THE POS. OR NEG.
BATTERY TERMINAL
|
CYCLE THROUGH THE HOIST LIFTING
CIRCUIT SEVERAL TIMES TO REMOVE
BATTERY SURFACE CHARGE
|
WITH MAST IN THE LOWER POSITION,
POWER STEERING MOTOR RUNNING,
CHECK VOLTAGE DROP ACROSS EACH
BATTERY CELL USING A VOLT-OHM
METER (2.5 VOLT SCALE)
|
CHECK FOR LESS THAN .05 VOLTAGE
DIFFERENCE BETWEEN EACH CELL. A
20 AMP LOAD MUST BE MAINTAINED
Troubleshooting
|
LESS THAN 100MA
|
BATTERY IS NOT LEAKING
EXCESSIVELY OR
SHORTED. WILL NOT
LIKELY AFFECT SCR
CIRCUIT OPERATION
|
|
|
3
|
SPECIFIC GRAVITY
|
|
|
|
USING A HYDROMETER, CHECK
|
SPECIFIC GRAVITY BETWEEN BATTERY
——→
CELLS. NO MORE THAN FIVE TO TEN
POINTS DIFFERENCE. (FULLY
CHARGED)
|
CORRECTED
BATTERY IS IN GOOD CONDITION
ADD 1,400 ELECTROLYTE TO RAISE OR
DISTILLED WATER TO LOWER.
RECHARGE FOR 1 1/2 HOURS TO MIX
|
|
|
|
CORRECTED
|
BATTERY IS
IN GOOD
CONDITION
|
|
|
|
TEST
|
|
|
|
|
|
|
INCORRECT
|
|
|
|
|
|
|
|
INCORRECT
|
REPLACE
BATTERY
AND
CONTACT
VENDOR
19