Input, Output And Led Settings; Digital Input Configuration - Eaton EDR 3000 Installation, Operation And Maintenance Manual

Hide thumbs Also See for EDR 3000:
Table of Contents

Advertisement

Input, Output and LED Settings

Digital Input Configuration

The State of the Digital Inputs can be checked within menu:
[Operations/Status Display/Name of the assembly group (e.g. DI-8X)]
The Digital Inputs can be configured within menu:
[Device Para/Digital Inputs/Name of the assembly group (e.g. DI-8X)/Group X]
Set the following parameters for each of the digital inputs:
»Nominal voltage«;
»Debouncing time« : A state change will only be adopted by the digital input after the debouncing time has expired;
and
»Inverting« (where necessary).
Inverting
Input Signal
Nom Voltage
The debouncing time will be started each time the state of the input signal alternates.
In addition to the debouncing time that can be set via software, there is always a hardware
debouncing time (approx 12 ms) that cannot be turned of.
EDR-3000
Debouncing Time
t
0
www.eaton.com
DI Slot X.DI x
XOR
State of the Digital Input.
IM02602003E
63