WAGO I/O System 750
750-940 EnOcean RS-485 Gateway; 868 MHz
3.4.1
DIP Switch Settings
The EnOcean Gateway hardware properties are set with the four-position DIP
switch ("DIP2").
Figure 10: Four-Position DIP Switch ("DIP2") for Configuring the EnOcean Functions
Table 10: DIP Switch Panel for Configuring the EnOcean Functions
DIP
Switch
1
2
3
4
*
Default setting
)
When the Modbus protocol is selected with the four-position DIP switch ("DIP1"),
other settings for Modbus mode are made with the eight-position DIP switch.
Exception: DIP switch 8 functions for the ESP3 and Modbus protocols.
Figure 11: Eight-Position DIP Switch ("DIP1") for Configuring the RS-485 Interface
Table 11: DIP Switch Panel for Configuring the RS-485 Interface
DIP
Switch
1
2
3
4
5
6
7
8
*
)
Default setting
Meaning
Function in
ON Position
LED functionality
LED "DS" switched off
Repeater mode
Repeater operation
Antenna type
External antenna active
Protocol selection
Modbus protocol active
Meaning
Function in
ON Position
Address 0
Setting the address LSB
Address 1
Setting the address
Address 2
Setting the address
Address 3
Setting the address MSB
Baud rate A
Baud rate setting
Baud rate B
Baud rate setting
Termination
RS-485 termination switched
off
BIAS network
Switched on (effective with
ESP3 and Modbus
protocols)
Version 1.3.0, valid from FW/HW Version 01/01
List of Figures
Function in
OFF Position
LED "DS" switched on *
Protocol selection *
)
Internal antenna active *
ESP3 protocol active *
Function in
OFF Position
See Table "Bit-Coded
Modbus Address."
See Table "DIP Switch
Positions for Selecting Baud
Rate."
RS-485 termination switched
on *
)
Switched off *
)
(effective with
ESP3 and Modbus
protocols)