Table 24: Information about existing module diagnostics

Global Diagnostics
Diagnostics
Low voltage of U
Low voltage of U
Pos : 30.10 /Serie 767 ( WAGO-SPEED WAY)/Parametrier en/I/O-Module/Parametrier ung Kanaldi agnosen Kurz schl uss/Überlas t Aktor @ 8\mod_1278414485725_21.doc x @ 59134 @ @ 1

Table 25: Information about an existing channel diagnostic

Channel Diagnostics
Diagnostics
Actuator short
circuit/overload
Pos : 30.11 /Serie 767 ( WAGO-SPEED WAY)/Parametrier en/I/O-Module/Parametrier ung Kanaldi agnosen U nterbr echung 48xx @ 8\mod_1278481912988_21.doc x @ 59214 @ @ 1
Actuator open load
Pos : 30.12 /Serie 767 ( WAGO-SPEED WAY)/Parametrier en/I/O-Module/Parametrier ung Kanaldi agnosen Ü bertemper atur 48xx @ 10\mod_1306933498784_21.doc x @ 73520 @ @ 1
Overtemperature
Pos : 30.13 /Serie 767 ( WAGO-SPEED WAY)/Wichtige Erläuter ung en/Sic herheits hinweise/Hinweis/Hi nweis : U nterbrechung S-BU S 48er @ 8\mod_1278393489593_21.doc x @ 59044 @ @ 1
Interruption of the S-BUS
If there is an interruption of the S-BUS, the module is automatically put in STOP
mode. The module outputs are disabled.
Pos : 30.14 /D okumentati on allgemei n/Gli ederungsel emente/---Seitenwec hs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Manual
Version 1.1.0
Description
LS
If an undervoltage of the logic and sensor supply U
on the module, the outputs are disabled and a corresponding diagnostic
is transmitted to the fieldbus coupler. The F-LED of the module
illuminates.
LS
If an undervoltage of the actuator supply U
module, the outputs are disabled and a corresponding diagnostic
transmitted to the fieldbus coupler. The module F-LED illuminates.
Description
The module has identified a short circuit or overload on the
corresponding channel (1 ... 8) (only enabled when the actuator output
is switched on).
The module has identified a disruption on the corresponding channel
(1 ... 8) only enabled when the actuator output is switched off).
The module has identified overheating on the corresponding channel
(1 ... 8) (only enabled when the actuator output is switched on).
Disabling the outputs.
If there is an undervoltage of U
module outputs are disabled. Machine components can
be placed in a dangerous condition, as well as
personnel and machine put in danger.
Disabling the outputs.
If there is an undervoltage of U
module outputs are disabled. Machine components can
be placed in a dangerous condition, as well as
personnel and machine put in danger.
Parameterizing
and/or U
, the
A
LS
of < 18 V occurs
LS
and/or U
, the
A
LS
of < 18 V occurs on the
A
53