Parameterizing
Pos : 30.6 /Serie 767 (WAGO-SPEED WAY)/Par ametrieren/I/O-M odule/Parametri erung 767- xxxx Di agnoseübersic ht_1 @ 14\mod_1360836957753_21.doc x @ 111870 @ 2 @ 1
7.2

Diagnostic Overview

The currently pending diagnostics existing on the module are displayed here. In
this view of the DTM, you can enable simulation of the diagnostics, as well as
disable transmission of the diagnostics. When disabling transmission, make sure
that the display behavior of each LED changes that indicates the specific
diagnostics (section "Diagnostics" > "LED Signaling"). The diagnostic overview
is only available in online mode.
Figure 19: Example of the diagnostic overview of a module (information may differ from the
actual module)
Pos : 30.7 /Serie 767 (WAGO-SPEED WAY)/Par ametrieren/I/O-M odule/Parametri erung 767- xxxx Di agnoseübersic ht_2 @ 7\mod_1265811272140_21.doc x @ 50279 @ @ 1

Table 23: Diagnostics setup

Parameter
Insert in PI
Simulation
Status
Pos : 30.8 /Dokumentation allgemei n/Glieder ungs elemente/---Seitenwechs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
767-4804/000-800 8DO 24V DC 2.0A IF (4xM12)
Description
By unselecting the checkbox, you specifically suppress evaluation and
transmission of individual diagnostics. Doing so has no effect on the
size of the process image. Even if a diagnostics has occurred, the
diagnostic value "0" (no error) is transmitted to the higher-level
controller.
If you have selected the "Insert in PI" checkbox, the "Simulation"
parameter is released. You can select the diagnostics you want to
simulate. Click the [Write] button to transfer the simulated values to the
module.
Displays whether there is a diagnostics:
X mark: There is a diagnostic message.
Check mark: There is no diagnostic message.