WAGO -SPEEDWAY 767 Manual page 64

8do 24v dc 2.0a if (4xm12) digital output module 24 v dc / 2.0 a
Hide thumbs Also See for WAGO-SPEEDWAY 767:
Table of Contents

Advertisement

64
Diagnostics
Table 30: Operating messages 1
Pos. LED Color/Status
15
SB
Pos : 42.5 /Serie 767 (WAGO-SPEED WAY)/Di agnose/I/O-Modul e/Betriebs mel dungen 767- xxxx DO/AO Allgemei n (Pos. 15, Teil 2) @ 7\mod_1268637553513_21.doc x @ 52463 @ @ 1
15
SB
Pos : 42.6 /Dokumentation allgemei n/Glieder ungs elemente/---Seitenwechs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Cause
Green and orange,
The set substitute value is
flashing, 1 Hz
applied to the module.
Orange, flashing,
The module has detected the
2 Hz
S-BUS.
Orange and green,
The last module is being
flashing, 4 Hz
detected in the 767 node.
Orange, flashing,
The fieldbus coupler is
1 Hz
addressing the module in the
767 node.
Orange and green,
The S-BUS parameters are
flashing, 2 Hz
being stored by the fieldbus
coupler.
Orange
The firmware is being
updated.
Orange, flashing,
The module is attempting to
4 Hz
establish communication with
the fieldbus coupler.
Green, flashing,
The module is in HOLD
1Hz
mode.
Green, flashing,
The module is in STOP
2Hz
mode.
767-4804/000-800 8DO 24V DC 2.0A IF (4xM12)
Is initiated by the fieldbus
coupler. The last values
transferred to the module are
kept.
Is initiated by the fieldbus
coupler. The output values are
set to 0.
WAGO-SPEEDWAY 767
Remedy/information
Can be set by the fieldbus
coupler if fieldbus is missing.
Check the fieldbus connection
and the status of the higher-
level controller.
-
Check the S-BUS terminator
and/or the S-BUS cables.
-
-
All 767 Series components
are being updated by the
fieldbus coupler within the
node.
Check the power supply to
upstream 767 Series
component and/or check the
S-BUS cable for damages.
Manual
Version 1.1.0

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

767-4804/000-800

Table of Contents