IOB2
AI10
IOB2
AI11
IOB2
AO1
IOB2
AO2
IOB2
AO3
IOB2
DI1
IOB2
DI2
IOB2
DI3
IOB2
DI4
IOB2
DO1
IOB2
DO2
IOB2
DO3
IOB2
DO4
IOB3
AI1
IOB3
AI2
IOB3
AI3
IOB3
AI4
IOB3
AI5
IOB3
AI6
IOB3
AI7
IOB3
AI8
IOB3
AI9
IOB3
AI10
IOB3
AI11
IOB3
AO1
IOB3
AO2
IOB3
AO3
IOB3
DI1
IOB3
DI2
IOB3
DI3
IOB3
DI4
IOB3
DO1
IOB3
DO2
SRDC-UG-2-14-000
19 Series Carrier®
SmartVu
Controls IOM
Motor Winding Temperature 3
Guide Vane1 Output
Head Pressure Output 2
Head Pressure Output
Evap Water Flow Switch
Cond Water Flow Switch
High Pressure Switch
Oil Heater Relay
Oil Pump Relay
Chiller Status(Discrete)
Vapor Source SV
Heat Reclaim Entering Temp
Heat Reclaim Leaving Temp
Remote Reset Sensor
Auto Water Temp Reset
[If Common Sensor Option is enable]
Common CHWS Temp
Auto Demand Limit Input
[If Common Sensor Option is enable]
Common CHWR Temp
Refrigerant Leak Sensor
Fire Security Interlock
[If ISM Input is disable]
Ice Build Contact
Chiller Alert Relay
REVISION
–
TM
2.3
DATE
PAGE
Dec 4, 2020
34 OF 168
Used for Analog type
guide vane actuator
User option
User option
User option, "Closed"
indicates "FLOW"
User option,"Closed"
indicates "FLOW"
user option,0=chiller
off, 1=chiller running
User option
User option
Used for lead lag
option
User option
Used for lead lag
option
User option
User option,normal
open
User option
User option, 24VAC
output, recommend
with external power
supply
34