DO1
IOB3
DO2
IOB3
DO3
IOB3
DO4
IOB3
AI1
IOB4
AI2
IOB4
IOB4
AI3
AI4
IOB4
IOB4
AI5
AI6
IOB4
AI7
IOB4
AI8
IOB4
AI9
IOB4
AI10
IOB4
AI11
IOB4
AO1
IOB4
AO2
IOB4
AO3
IOB4
DI1
IOB4
DI2
IOB4
DI3
IOB4
DI4
IOB4
DO1
IOB4
IOB4
DO2
DO3
IOB4
DO4
IOB4
SRDC-UG-2-14-000
19 Series Carrier®
TM
SmartVu
Controls IOM
Chiller Status(Discrete)
Chiller Alert Relay
Chilled Water Pump
Condenser Water Pump
[If Water Pressure Option is PD TRD
(transducers)]
Evap Enter Water Volts
[If Water Pressure Option is PD TRM
(transmitter)]
Chilled Water Pres Drop
[If Water Pressure Option is PD TRD
(transducers)]
Evap Leave Water Volts
[If Water Pressure Option is PD TRM
(transmitter)]
Cond Water Pres Drop
[If Water Pressure Option is PD TRD
(transducers)]
Cond Enter Water Volts
[If Water Pressure Option is PD TRD
(transducers)]
Leaving Cond Water Pressure
Evap Water Flow Measurement
Cond Water Flow Measurement
Chilled Water Pump (Variable)
Condenser Water Pump (Variable)
Tower Fan (Variable)
Power Request Feedback
Customer Alert
Free Cooling Start Switch
Free Cooling Mode
Power Request Output
Tower Fan High
Tower Fan Low
REVISION
–
2.3
DATE
PAGE
Dec 4, 2020
28 OF 168
User option
User option, 24VAC
output, recommend
with external power
supply
User option
User option
User option
User option
User option
User option
User option, 4~20mA
User option, 4~20mA
Marine option
User option
User option
User option
Marine option
User option
User option
28