UC240 UltraSync Communicator Installation Guide for 2X-A/2X, KFP-A, and ZP2-A/ZP2 Fire Alarm Control Panels P/N 10-9000-501-UC24-02 • ISS 17NOV22...
Note messages advise you of the possible loss of time or effort. They describe how to avoid the loss. Notes are also used to point out important information that you should read. UC240 UltraSync Communicator Installation Guide for 2X-A/2X, KFP-A, and ZP2-A/ZP2 Fire Alarm Control Panels...
Once registered with the Carrier UltraSync portal, the UC240 allows notifications to be sent to: • Central Monitoring Stations (CMS) • Email addresses • Supported mobile apps (IOS and Android) Figure 1: UC240 Communicator UC240 UltraSync Communicator Installation Guide for 2X-A/2X, KFP-A, and ZP2-A/ZP2 Fire Alarm Control Panels...
If direct glanding is not possible, interface cables should be enclosed in conduits to provide mechanical protection. Once all wiring is completed, secure the lid to the SMB-DIN2 using the screws provided. UC240 UltraSync Communicator Installation Guide for 2X-A/2X, KFP-A, and ZP2-A/ZP2 Fire Alarm Control Panels...
Page 7
The device can be programmed via the device interface or the UltraSync+ mobile app (available for Android and IOS mobile devices). See “Configuration Utility configuration and UC240 programming” on page 7 for information on configuration and programming. UC240 UltraSync Communicator Installation Guide for 2X-A/2X, KFP-A, and ZP2-A/ZP2 Fire Alarm Control Panels...
Page 8
Figure 3: SMB-DIN2 lid screws Figure 4: UC240 installation (DIN rail) Figure 5: UC240 installation (inside lid) Figure 6: UC240 installation location Figure 7: UC240 installation location UC240 UltraSync Communicator Installation Guide for 2X-A/2X, KFP-A, and ZP2-A/ZP2 Fire Alarm Control Panels...
See Figure 9 on page 6 for interfacing fault input. • See “Fire routing delay configuration for the 2010-2-PIB” on page 8 for fire routing delay configuration. UC240 UltraSync Communicator Installation Guide for 2X-A/2X, KFP-A, and ZP2-A/ZP2 Fire Alarm Control Panels...
Page 10
Event reporting only. This option is compatible with any 2X-A/2X, KFP-A, ZP2- A/ZP2 control panel variant. Figure 9: Non-EN 54-21 compliant option (panel inputs, fire and fault relay outputs) UC240 UltraSync Communicator Installation Guide for 2X-A/2X, KFP-A, and ZP2-A/ZP2 Fire Alarm Control Panels...
Table 3: Input 2 (only for EN 54-21 installations) Parameter Configuration OpMode Fire Routing Ack Type 1 Control Enabled Description Dialer/CMS Ack Zone None Figure 11: Configuration Utility Input 2 configuration UC240 UltraSync Communicator Installation Guide for 2X-A/2X, KFP-A, and ZP2-A/ZP2 Fire Alarm Control Panels...
Page 12
Configuration window (Group ID 971), as shown below. The delay must be configured for each zone. Figure 13: Configuring the fire routing delay in the Zone Configuration window UC240 UltraSync Communicator Installation Guide for 2X-A/2X, KFP-A, and ZP2-A/ZP2 Fire Alarm Control Panels...
5. Go to Output Type and change the Output3 setting to Fire Ack. Press ↵ for 3 seconds to save. 6. Write down your SID number and Web Pass Code in a safe place. Figure 14: Web pass code location UC240 UltraSync Communicator Installation Guide for 2X-A/2X, KFP-A, and ZP2-A/ZP2 Fire Alarm Control Panels...
Page 14
Figure 15: Programming menus Figure 16: Signal strength UC240 UltraSync Communicator Installation Guide for 2X-A/2X, KFP-A, and ZP2-A/ZP2 Fire Alarm Control Panels...
(System Trouble). R323908 should be R300908 (Alarm Relay). Surgard SIA BA908 BA908 BR908 Should be SIM 2/4G FT908 (Fire Trouble). BR908 Should be FR908 (Fire Restoral). UC240 UltraSync Communicator Installation Guide for 2X-A/2X, KFP-A, and ZP2-A/ZP2 Fire Alarm Control Panels...