3.1.2. ISM (Integrated Starter Module)
ISM is motor control module for fixed speed or free standing VFD configuration, and it is supplied from
an 115VAC supply referred to earth.
ISM input / output description is as below:
DESCRIPTION
STARTER FAULT
COMPRESSOR START CONTACT
COMPRESSOR RUN CONTACT
LINE VOLTAGE V1
LINE VOLTAGE V2
LINE VOLTAGE V3
LINE CURRENT C1
LINE CURRENT C2
LINE CURRENT C3
GROUND FAULT PHASE 1
GROUND FAULT PHASE 2
GROUND FAULT PHASE 3
VFD SPEED FEEDBACK
VFD TARGET SPEED
COMPRESSOR START RELAY
COMPRESSOR TRANS RELAY
SHUNT TRIP RELAY
SRDC-UG-2-14-000
19 Series Carrier®
–
TM
SmartVu
Controls IOM
POINT NAME
STARTFLT
STAR_AUX
RUN_AUX
LN_VOLT1
LN_VOLT2
LN_VOLT3
LN_AMPS1
LN_AMPS2
LN_AMPS3
GRFLT_31
GRFLT_23
GRFLT_12
VFD_IN
VFD_OUT
COMP_SR
TRANS
TRIPR
REVISION
DATE
2.3
Dec 4, 2020
TYPE
NUMBER
Dry
J2-7,8
Contact
Dry
J2-9,10
Contact
Dry
J2-11,12
Contact
0-5 Volt
J3-1
0-5 Volt
J3-2
0-5 Volt
J3-3
0-5 Volt
J4-1,2
0-5 Volt
J4-3,4
0-5 Volt
J4-5,6
0-5 Volt
J5-1,2
0-5 Volt
J5-3,4
0-5 Volt
J5-5,6
0-10 Volt/
J6-1,2
0-5 Volt
0-20 mA
J8-1,2
Relay
J9-1,2
J9-3,4
Relay
J9-5,6
Relay
PAGE