tmramprt
0.56 to 5.56
1 to 10
13
rcysh_dt
0.28 to 2.22
0.5 to 4
14
rcyst_dt
1.11 to 5.56
2 to 10
15
dmp_min
0 to 30
16
dmp_max
60 to 100
17
dmp_step
1.5 to 20
18
dmp_intv
5 to 30
19
dmp_alm
60 to 600
20
dmp_dly
1 to 5
21
dmp_cldb
13.79 to 68.95
2 to 10
22
dmp_opdb
68.95 to 137.90
10 to 20
23
dmp_gain
0 to 10
24
dmp_dt
2.22 to 5.56
4 to 10
25
oilpvr_t
15 to 300
26
wflow_t
0.5 to 5
27
sf_st_th
40 to 100
28
mbb_pfcl
0.5 to 2
29
ex_start
NO_YES
30
oilstiro
0 to 3
31
blank
-
SRDC-UG-2-14-000
19 Series Carrier®
TM
SmartVu
Controls IOM
1.67
^C
3
^F
0.56
^C
1
^F
5.56
^C
10
^F
2
%
85
%
5
%
10
sec
180
sec
2
min
34.48
kPa
5
PSI
89.64
kPa
13
PSI
1
-
3.89
^C
7
^F
180
sec
5
min
100
%
1
-
NO
-
1
-
-
-
REVISION
DATE
2.3
Dec 4, 2020
Temp Ramp per Min
Recycle Shutdown Delta T
Recycle Restart Delta T
ECO DMP VLV Min Pos
ECO DMP VLV Max Pos
ECO DMP VLV Speed Step
ECO DMP VLV Out Interval
ECO DMP VLV Fault Time
ECO DMP VLV Act Delay
ECO DMP VLV Close DB
ECO DMP VLV Open DB
ECO DMP VLV Gain
ECO DMP VLV Act Delta T
Lub Press Verify Time
Water Flow Verify Time
Soft Stop Amps Threshold
Power Calibration Factor
Enable Excessive Starts
Oil Stir Cycle(19XR6/7)
No Stir=0, 30s/30m=1,
PAGE
149 OF 168
149