IOB1
DO4
IOB2
AI1
IOB2
AI2
IOB2
AI3
IOB2
AI4
IOB2
AI5
IOB2
AI6
IOB2
AI7
IOB2
AI8
IOB2
AI9
IOB2
AI10
IOB2
AI11
IOB2
AO1
IOB2
AO2
IOB2
AO3
IOB2
DI1
IOB2
DI2
IOB2
DI3
IOB2
DI4
IOB2
DO1
IOB2
DO2
IOB2
DO3
IOB2
DO4
IOB3
AI1
IOB3
AI2
IOB3
AI3
IOB3
AI4
IOB3
AI5
SRDC-UG-2-14-000
19 Series Carrier®
TM
SmartVu
Controls IOM
Chiller Status(Discrete)
Motor Winding Temperature 1
Motor Winding Temperature 2
Motor Winding Temperature 3
Oil Supply Temperature
Oil Sump Temperature
Oil Supply Pressure
Oil Sump Pressure
Auto Demand Limit Input
EC Valve Feedback
Bearing Shaft Displacement Sensor
Guide Vane1 Output
Damper Valve Output mA
EC Valve Output mA
Damper Valve Feedback Fully Open
Damper Valve Feedback Fully Close
High Pressure Switch
[If ISM Input is disable]
Ice Build Contact
Oil Heater Relay
Oil Pump Relay
[If vapor source valve is disabled]
Economizer Damper Valve Open
[If vapor source valve is disabled]
Economizer Damper Valve Close
[If vapor source valve is enabled]
Vapor Source SV
Low Speed ME Brg Temp
Low Speed CE Brg Temp
High Speed ME Brg Temp
High Speed CE Brg Temp
Remote Reset Sensor
REVISION
–
2.3
DATE
PAGE
Dec 4, 2020
23 OF 168
user option , 0=chiller off,
1=chiller running
User option
Used f or Analog type
guide vane actuator
For analog type damper
valve
For digital type damper
valve
For digital type damper
valve
0=abnomal ,1=close
User option
For digital type damper
valve
For vapor source valve
User option
23
Need help?
Do you have a question about the SmartVu Control and is the answer not in the manual?
Questions and answers