Carrier SmartVu Control Manual page 147

For 19 series centrifugal chiller
Hide thumbs Also See for SmartVu Control:
Table of Contents

Advertisement

Name
Range
1
chil_typ
0 to 3
2
blank
-
3
blank
-
4
blank
-
5
blank
-
6
vfd_opt
0 to 9
7
blank
-
8
blank
-
9
blank
-
10
blank
-
11
blank
-
12
blank
-
13
blank
-
14
blank
-
15
blank
-
16
unit_typ
0 to 1
17
blank
-
18
ref_typ
0 to 2
19
blank
-
20
comp_typ
0 to 1
21
chmedium
WATER_BRINE
22
cond_typ
0 to 1
23
blank
-
24
comp_pre
0 to 1
25
blank
-
SRDC-UG-2-14-000
19 Series Carrier®
TM
SmartVu
Controls IOM
Default
Unit
0
-
-
-
-
-
-
-
-
-
0
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
0
-
-
-
0
-
-
-
1
-
WATER
-
0
-
-
-
0
-
-
-
REVISION
DATE
2.3
Dec 4, 2020
Displayed text*
Chiller Type
19XR6/7=0
19XR2~5/C/D/E/V=1
19DV=2
19XRF=3
VFD/Starter Option
Starter with ISM = 0
FS VFD with ISM = 1
Carrier 32VS VFD = 2
Rockwell LF2 VFD = 3
Eaton VFD = 4
Rockwell STD VFD = 5
Danfoss VFD = 7
Benshaw Starter = 8
STEP HV VFD = 9
Unit Type
Cool Only=0, Heat Mach=1
Refrigerant Type
R134a=0,R513A=1,R515A=2
Comp(1Stage=0, 2Stage=1)
Chilled Medium Type
Cond Refrig Shell MAWP
185PSI=0, 300PSI=1
Comp Refrig Press
44PSI=0, 72PSI=1
PAGE
147 OF 168